Delhi Fire Service ( Amendment) Rules, 2025
Delhi Gazette
SG-DL-E-26052026-272885
EXTRAORDINARY
PUBLISHED BY AUTHORITY
No. 143] DELHI, TUESDAY, MAY 26, 2026/JYAISTHA 5, 1948 [N. C. T. D. No. 58
HOME DEPARTMENT
NOTIFICATION
Delhi, the 26th May, 2026
F. No. DFS/HQ/Misc./2025/01(E-259159)/237.—In exercise of the
powers conferred by Section 63 of the Delhi Fire Service Act, 2007 (Delhi Act 2 of
2009), the Lieutenant Governor of the National Capital Territory of Delhi hereby
makes the following amendments in the Delhi Fire Service Rules, 2010, namely:
1. Short title and commencement-
(1) These Rules may be called the Delhi Fire Service (Amendment) Rules, 2025.
(2) They shall come into force on the date of their publication in the Official
Gazette except amendments of Rules 34, 35, 36, 37, 38, First Schedule and
Seventh Schedule.
(3)Amendments of Rules 34, 35, 36, 37, 38, First Schedule and Seventh Schedule
shall come into force after 90 days from the date of their publication in the
Official Gazette;
Provided that all applications pending on date of commencement shall be
processed under the provisions in force on the date of application.
2. In the Delhi Fire Service Rules, 2010 (hereinafter referred to as the Principal
Rules), in rule 2, –
(A) after clause (iv), the following shall be inserted, namely:
(iv-a) “Fire Safety Auditor” means a Third Party i.e., a person or an association of
persons or company as referred to in rules and the Seventh Schedule of these
Rules, duly empanelled with the Director of Delhi Fire Service.
(B) clause (v) is substituted, namely:
“Fire Safety Certificate” means the Fire Safety Certificate issued by the Fire
Service for compliance with the minimum standards for fire prevention and fire
safety of buildings or premises under the Principal Rules or by a Fire Safety
Auditor under these rules;
(C) clause (viii) is substituted, namely:
(viii) “National Building Code of India” means the Code made by Bureau of Indian
Standards; “Fire and Life Safety” published by Bureau of Indian Standards, New
Delhi, as amended from time to time.
(D) clause (xi) is substituted, namely:
(xi) “special area” means the special area as delineated in the Master Plan of
Delhi.
(E) in the clause(xiii), ‘National Building Code 2005’ shall be substituted with
‘National Building Code of India’.
3. In the Principal rules, rule 3, shall be substituted namely:
3. Constitution of Fire Zones
(1) There shall be five or more Fire Zones in National Capital Territory of Delhi as
per the contingencies of work namely, ‘Central Zone’, ‘East Zone’, ‘West Zone’,
‘North Zone’ and ‘South Zone’ or any other Zone, as may be created by the
Government by general or special order depending upon the exigencies of work.
(2) Each Fire Zone shall be under the charge of the Chief Fire Officer who may be
assisted by one or more Deputy Chief Fire Officers.
(3) The Central Fire Zone shall comprise of New Delhi, Central and Old Delhi
Divisions or any other Division as may be created depending upon exigencies of
work.
(4) The East Fire Zone shall comprise of North-East and East Divisions or any
other Division as may be created depending upon exigencies of work.
(5) The West Fire Zone shall comprise of West, South-West and North West
Divisions or any other Division as may be created depending upon exigencies of
work.
(6) The North Fire Zone shall comprise of North, Outer North and Central North
Divisions or any other Division as may be created depending upon the exigencies
of work.
(7) The South Fire Zone shall comprise of South and South East Division or any
other Division as may be created depending upon the exigencies of work.
4.In the Principal rules, rule 4, shall be substituted namely:
4. Constitution of Fire Divisions
(1) There shall be thirteen or more Fire Divisions in National Capital Territory of
Delhi as per the contingencies of work for the purpose of clause (b) of section 9 of
the Act, namely, ‘New Delhi Division’, ‘North Division’, ‘North-West Division’,
‘West Division’, ‘South-West Division’, ‘South Division’, ‘South-East Division’,
‘Central Division’, ‘North-East Division’, ‘Outer North Division’, ‘Old Delhi
Division’, ‘Central North Division’ and ‘East Division’ or any other Division, as
may be created by the Government by general or special order depending upon
the exigencies of work.
(2) Each Fire Division shall be under the charge of a Divisional Fire Officer.
(3) The New Delhi Division shall comprise of New Delhi and Delhi Cantonment
Sub-Divisions.
(4) The North Division shall comprise of Burari, Adarsh Nagar and Badli SubDivisions.
(5) The North-West Division shall comprise of Kirari, Nangloi Jat and Rohini SubDivisions.
(6) The West Division shall comprise of Vikaspuri, Janakpuri and Rajouri Garden
Sub-Divisions.
(7)The South-West Division shall comprise of Najafgarh, Matiala, Dwarka and
Bijwasan Sub-Divisions.
(8)The South Division shall comprise of Chhatarpur, Malviya Nagar, Deoli and
Mehrauli Sub-Divisions.
(9)The South-East Division shall comprise of Jangpura, Kalkaji and Badarpur
Sub-Divisions.
(10)The Central Division shall comprise of Patel Nagar and Karol Bagh SubDivisions.
(11)The North-East Division shall comprise of Karawal Nagar, Gokulpur, Yamuna
Vihar and Shahdara Nagar Sub-Divisions.
(12)The Outer North Division shall comprise of Mundka, Narela and Bawana SubDivisions.
(13)The East Division shall comprise of Gandhi Nagar, Vishwas Nagar and
Patparganj Sub-Divisions.
(14) The Central North Division shall comprise of Shakur Basti, Shalimar Bagh
and Model Town Sub-Divisions.
(15) The Old Delhi Division shall comprise of Sadar Bazaar and Chandani Chowk
Sub-Divisions.
5. In the Principal rules, rule 5, sub-rule (1) shall be substituted namely:
(1) There shall be Thirty-Nine or more fire sub divisions namely; New Delhi,
Delhi Cantonment, Patel Nagar, Karol Bagh, Sadar Bazaar, Chandni Chowk,
Karawal Nagar, Gokulpur, Yamuna Vihar, Shahdara, Gandhi Nagar, Vishwas
Nagar, Patparganj, Burari, Adarsh Nagar, Badli, Mundka, Narela, Bawana,
Shakur Basti, Shalimar Bagh, Model Town, Chhatarpur, Malviya Nagar,
Deoli, Mehrauli, Jangpura, Kalkaji, Badarpur, Vikaspuri, Janakpuri, Rajouri
Garden, Najafgarh, Matiala, Dwarka, Bijwasan, Kirari, Nangloi Jat and
Rohini Sub-Divisions in the National Capital Territory of Delhi as per the
exigencies of work for the purposes of clause (b) of section 9 of the Act.
6. In the Principal Rule 8, ‘Master Plan Delhi 2021’ shall be substituted with
‘Master Plan of Delhi, as amended from time to time’.
7. In the Principal rules 20, ‘DDO Headquarters, Delhi Fire Service payable at
Delhi’ shall be substituted with ‘DDO Headquarters, Delhi Fire Service payable at
Delhi or through online payment gateway’.
8. In the Principal rule 22, ‘Principal, FSMA or DDO concerned’ shall be
substituted with ‘Principal, FSMA or DDO concerned or through an online
payment gateway’.
9. In the Principal rule 25, ‘Principal or DDO concerned through a bank draft’
shall be substituted with ‘Principal or DDO concerned through a bank draft or
through an online payment gateway’.
10. In the Principal rules, rule 26, shall be substituted namely:
26.(1) “The rules of chapter V shall regulate the owner or occupiers, or both, of
premises or buildings or erectors of pandals, for the provisions of section 25 of
the Act, unless and otherwise specified in the Rule”;
(2) In addition to other branches in Fire Service, there shall be constituted a
branch namely ‘Fire Prevention Wing’ under Section 25 of the Act within the
Fire Service Headquarters;
(3) The Headquarter shall be under the charge of a Chief Fire Officer assisted by
such other Group ‘A’, ‘B’ and ‘C’ fire officers and other members of fire service, as
determined by Director;
Provided that the Director may, based on the workload, increase or decrease the
number and rank of fire officers in any category at Headquarters.
(4) The Fire Service Headquarters, in consideration of the efficient
management of fire prevention activities, fire-ground operations, and
maintenance of the fire service, shall control and regulate the following:
(a) Policy formulation and strategic planning;
(b) Resource management;
(c) Functions of Administrative branch;
(d) Execution of statutory provisions of the DFS Act & Rules;
(e) Litigation supervision and technical avowals;
(f) Coordination with Zones, FSMA, and monitoring of all other branches of
the fire service;
The Headquarters shall set the overall direction and strategy of the fire service by
providing core administrative support for all the branches to ensure that policies
are effectively executed across the fire service.
(5)‘Fire Prevention Wing’: The Fire Prevention Wing shall be under the charge of a
fire officer not below the rank of a Deputy Chief Fire Officer, and assisted by other
Group ‘A’, ‘B’ and ‘C’ fire officers and other members of fire service;
The ‘Fire Prevention Wing’ shall examine the building plans along with Fire Safety
Schemes duly certified by a Fire Safety Auditors of Level-2 and Level-3 as per
their authorization under the rules, referred to Fire Service by local authority or
any other statutory authority, from fire prevention and fire safety point of view
and issue directives relating to fire prevention and fire safety measures for
compliance by the builder, owner or occupier.
11. In the Principal rules, Rule 27 shall be substituted namely:
27. Classes of occupancies likely to cause a risk of fire.
The following classes of occupancies for the purposes of sub-section (1) of section
25 of the Act shall be construed to likely cause a risk of fire, namely:
(1) Pandal having seating capacity more than 50 persons or covered area more
than 50 square meters.
(2) Residential buildings (other than hotels and guest houses) having height more
than 15 meters or comprised of Five or more stories, including mezzanine/stilt
floor above ground level.
(3) Hotels and guest houses building having height more than 12 meters or
comprised of four or more stories, including mezzanine/stilt floor above
ground level.
(4) Educational buildings having height more than 9 meters or comprised of
three or more stories, including mezzanine/stilt floor above ground level.
(5) Institutional buildings having height more than 9 meters or comprised of
three or more stories, including mezzanine/stilt floor above ground level.
(6) All Assembly buildings.
(7) Business buildings having height more than 15 meters or comprised of five or
more stories, including mezzanine/stilt floor above ground level.
(8) Mercantile buildings having height more than 9 meters or comprised of three
or more stories, including mezzanine/stilt floor above ground level.
(9) Industrial buildings having covered area on all stories more than 250 square
meters.
(10) Storage buildings having covered area on all stories more than 250 square
meters.
(11) All Hazardous buildings having covered area on all stories more than 100
square meters.
(12) Underground Structures comprising of two or more Levels.
12. In the Principal Rule 29, ‘IS 8758:1983’ and ‘National Building Code of India,
2005’ shall be substituted with ‘IS 8758’ and ‘National Building Code of India’
respectively.
13. In the Principal rules, in rule 32, the following shall be substituted:
(A). In sub-rule (1): Form ‘M’ with Form ‘N’
(B).In sub-rule (2): ‘DDO (Headquarters), Delhi Fire Service payable at Delhi’ with
‘DDO (Headquarters), Delhi Fire Service payable at Delhi or through an online
payment gateway’.
14. In the Principal rules 33, ‘National Building Code of India 2005’ shall be
substituted with ‘National Building Code of India’.
15. In the Principal rules, in rule 34:
(A). the sub-rule (2) shall be omitted.
(B). the sub-rule (3) shall be substituted and renumbered as sub-rule (2) namely:
(2) The Fire Prevention Wing shall direct the Fire Safety Auditor, Owner, occupier,
or the Architect through Local Authority or any statutory authority to modify the
building plans and schemes received under sub-rule (1) above to ensure the
compliance with these rules and the Fire Safety Auditor, Owner, occupier, or the
Architect shall abide by such instructions failing which building plans are liable
for rejection.
(C). the sub-rule (4) shall be substituted and renumbered as sub-rule (3) namely:
(3) The fire prevention and fire safety measures shall be issued within three
weeks from the date of submission under sub-rule (1) or submission of modified
building plans and schemes under sub-rule (2).
16. In the Principal rules, rule 35 shall be substituted namely:
35. Issue of Fire Safety Certificate
(1) For the purpose of issuance of the Fire Safety Certificate by a Fire Safety
Auditor, owner or occupier of a premise or building or occupancy shall engage a
Fire Safety Auditor from the list of Fire Safety Auditors on the portal of Delhi Fire
Service. The Fire Safety Certificate issued by a Fire Safety Auditor shall be
deemed to be issued under the delegated authority of the Director and shall be
subject to verification under the Act.
(2) The Fire Safety Auditor shall possess the requisite qualifications, experience,
and other criteria as specified in Seventh Schedule.
(3) The engaged Fire Safety Auditor shall conduct a thorough inspection of the
premise or building or occupancy, including all fire prevention and fire safety
measures, and shall submit a detailed inspection report in Form ‘J’ and issue a
Fire Safety Certificate in Form ‘H’ and declaration in Form ‘I’ under this rule to
the owner or occupier of those buildings or occupancies, which are identified
under Rule 27, and/or which require clearance from Delhi Fire Service;
Provided that issuance of Fire Safety Certificate by a Fire Safety Auditor shall not
absolve the owner or occupier of primary responsibility for maintaining fire
prevention and fire safety measures under the Act;
Provided further that the Delhi Fire Service shall not be liable for any loss or
damage arising out of certification issued by a Fire Safety Auditor, except where
malafide or gross negligence is attributable to Fire Service officers.
(4) The Fire Safety Auditor or the owner or the occupier as identified in sub-rule
(3) shall make online submission of the following to the Director:
a) Fire Safety Certificate in Form ‘H’
b) Declaration in Form ‘I’
c) Inspection report in Form ‘J’
d) Fee of Rupees One Thousand through bank draft/pay order to the DDO
(Headquarters), Delhi Fire Service payable at Delhi or through an online
payment gateway.
(5) The Director shall maintain all the records submitted under sub-rule
(4). The fire officer or a team of fire officers under the provisions of Delhi Fire
Service Act and rules, shall randomly inspect Fire Safety Certificates issued by
Fire Safety Auditors.
Provided that not less than five percent of certificates issued by Fire Safety
Auditors in a quarter shall be subject to random inspection.
(6) On the reporting of any deficiency in the fire prevention and fire safety
measures after the inspection carried out by the fire officer(s) under the Act and
Rules or for any falsification in the report of the Fire Safety Auditor, the Director
may initiate proceedings against the owner or occupier and/or the Fire Safety
Auditor, after giving them an opportunity to present their case, under the
provisions of the Act and Rules.
(7) No Fire Safety Auditor shall audit any building for which he or his firm has
provided design, consultancy, installation or maintenance services.
(8) The Fire Safety Auditor engaged by owner or occupier under these Rules, shall
be deemed to be a public servant as specified in sub-section (28) (k) (i) of Section
2 of the Bharatiya Nyaya Sanhita 2023 for the purpose of these Rules.
17. In the Principal rules, Rule 36 shall be substituted namely
36. Duration of Fire Safety Certificate:-
(1) The Fire Safety Certificate issued under Rule 35 unless suspended or
cancelled by Delhi Fire Service under the provisions of Delhi Fire Service Act and
Rules shall remain valid, subject to the submission of Form ‘K’ every year.
(2) The Fire Safety Auditor or the Fire Safety Officer or the owner or the occupier
shall submit online declaration in Form ‘K’ of the first schedule, prior to the
completion of one year from the issuance date of Fire Safety Certificate or Form
‘K’ submitted on last occasion.
(3) The premise or buildings or occupancies already issued with Fire Safety
Certificates prior to the promulgation of these Rules and which are still having
validity under the Principal Rules shall be deemed to have been issued Fire Safety
Certificate under these Rules and their validity shall be governed by sub-rule (1).
18. In the Principal rules, Rule 37 shall be substituted namely:
37. Automated Continuous Monitoring System
In classes of occupancies as identified in sub-rule (2) to (12) of Rule 27 for the
purpose of sub-rule (1) of Rule 38, an Automated Continuous Monitoring System
for fire prevention and fire safety measures or part thereof, shall be provided by
the owner or occupier of the premise or building as specified in Seventh
Schedule;
Provided that the ACMS shall comply with such technical standards and cyber
security protocols as may be notified by the Director.
19. In the Principal Rule 38, the sub-rule (2) shall be substituted namely:
(2) Every year, the following online submission shall be made to the Director by
owner or occupier or by Fire Safety Auditor or by Fire Safety Officer appointed
under section 29 of the Act, as the case may be:
a) Declaration in Form ‘K’
b) Fee of Rupees One Thousand through bank draft/pay order to the DDO
(Headquarters), Delhi Fire Service payable at Delhi or through an online payment
gateway.
20. In the Principal rule 40, ‘any other officer’ shall be substituted by ‘any other
fire officer’.
21. In the Principal rules 42, ‘DDO (Headquarters), Delhi Fire Service payable
at Delhi’ shall be substituted with ‘DDO (Headquarters), Delhi Fire Service
payable at Delhi or through an online payment gateway’.
22. In the Principal rules, Rule 43 shall be substituted namely:
43.Compounding of offences.
(1) The Deputy Chief Fire Officer may compound offences under sub-section (1) of
section 54 of the Act, punishable with fine up to and including ₹ 10,000 (rupees
ten thousand only).
(2) The compounding limit for the Chief Fire Officer for purposes under sub-rule
(1) shall be ₹50,000 (rupees fifty thousand only).
(3) The Director may compound any offence under section 54 of the Act and
under these rules punishable with fine exceeding ₹50,000 (rupees fifty thousand
only).
(4) All such compounding fee shall be deposited with DDO (Headquarters), Delhi
Fire Service through bank draft/pay order payable at Delhi or through an online
payment gateway.
23.In the Principal rules, in rule 47, the sub-rule (1) shall be substituted namely:
(1) The Director, Chief Fire Officer and Deputy Chief Fire Officer of Fire Service
may sanction rewards by way of certificate or cash rewards or with both to public
or members of Fire Service up to the limits noted against each hereunder:
Sr.
No.
Authority
competent to
sanction
Type of
commendation
Cash Rewards
1 Director Commendation
Roll
Up to ₹1,00,000 in each case for actions
of outstanding merit subject to budget
limit.
2 Chief Fire
Officer
Commendation
Certificate Class I
Up to ₹75,000 in each case for actions
of special merit as to deserve a higher
form of recognition than a Deputy Chief
Fire Officer is empowered to give.
3 Deputy Chief
Fire Officer
Commendation
Certificate Class II
Up to ₹50,000 in each case in
recognition of specific instances of
exemplary performance or assistance to
Fire Service on the occasion of fire
and/or rescue operations.
Provided that the Government may, on the recommendation of the Director, in
each case, may grant rewards more than ₹1,00,000 (Rupees one lakh) in
recognition of specific instances of exemplary performance by the members of Fire
Service or member of the public for assistance to Fire Service on the occasion of
fire and/ or rescue operations.
24. The Director Fire Service, may notify a date after which any payment shall
be received exclusively through the online payment gateway of the Directorate of
Fire Service.
25. In the Principal Rules, the Form ‘B’ in the First Schedule shall be substituted
namely:
FORM ‘B’: APPLICATION FOR STAND-BY DUTY
[See sub-rule (2) of rule 20]
To
The Director
Delhi Fire Service
Delhi Fire Service Headquarters
Connaught Place
New Delhi-110 001.
Sub: Application for providing stand-by duty
at……………………………………………………………… (address of the place where
stand-by duty is required).
Sir,
Please provide stand-by ………………………… (name of vehicle) at the
aforesaid address with effect from ……………hrs. to ………… hrs. on
…………………………… (date to be mentioned) during the
……………………………………………………………………
……………………… (occasion to be mentioned for which required).
The required payment of ₹ …………………. is enclosed through bank draft
No……………………… dated …………………… drawn on
…………………………………….in favour of DDO, Headquarters, Delhi Fire Service
OR an online payment gateway transaction ID……………………………………….
Dated:
(Signature of the applicant)
Contact details:
Name in full……………………………………………….
Email ID ………………………………………………….
Tel. No. …………………………………………………….
Mobile No. …………………………………………………
26.In the Principal Rules, the Form ‘H’ in the First Schedule shall be substituted
namely:
FORM ‘H’
FIRE SAFETY CERTIFICATE BY FIRE SAFETY AUDITOR
[See rule 35(3)]
UID No…………………………. Dated: …………….
FIRE SAFETY CERTIFICATE
Certified that the ………………………….……………….…………….. (name of the
building/premises or entity) situated
at……….………………………………………………………………(address) comprised of
…………………basement(s) and …………………(upper floors) owned/occupied by
…………………………………………(name of the company / name of the
owner/occupier)have complied with the fire prevention and fire safety
requirements in accordance with rule 33 of the Delhi Fire Service Rules, 2010
and verified by undersigned on ……………………… (date of inspection)in the
presence of…………………………………………………(name and address of the
owner/occupier or his representative) and that the building/premises is fit for
occupancy class ……….………………………………………………………with effect
from …………………………….subjected to conditions of Rule 36 and 38 unless
suspended or cancelled by Delhi Fire Service under the provision of DFS and
Rules-2010 as amended from time to time.
Issued on ………………………… at New Delhi by
Dated…………………….
Signature………………………………………….
Name of the Fire Safety Auditor………………….
Email ID…………………………………………………………
Telephone No………………………………. …………….
Mobile No……………………………………………………….
Level of Fire Safety Auditor ……… and Registration No……………..
Stamp……………………………………………………………..
Copy to:
1. __________________________________________________________
2. __________________________________________________________
Conditions for the validity of fire safety certificate:
1. All the means of escape/entry/exit shall be kept free from any obstruction.
2. All the fire safety arrangements provided therein shall be maintained in good
working condition at all time.
3. Any loss of life or property due to non-functional fire safety measures shall be
at the responsibility of the owner/occupier.
4. All the staff members must know the correct method of operation of
firefighting system.
5. The owner/occupier or Fire Safety Officer or Fire Safety Audit or shall submit
yearly declaration in Form ‘K’ [sub-rule (2) of Rule 38] provided in the first
schedule of Delhi Fire Service Rules 2010.
6. This fire safety certificate may not in any way be treated as regularization of
unauthorized construction or Alteration, if any.
7. “The owner/occupier shall ensure for timely submission of Form ‘K’ for
continuation of this certificate as stipulated in Rule 36 through another Fire
Safety Auditor.”
Verification by the Fire Officer(s)
[Under Rule 35]
The Fire Safety Certificate issued by the Fire Safety Auditor stand suspended or
cancelled and annulled due
to………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………… (reasons to be recorded).
OR
The Fire Safety Certificate issued by the Fire Safety Auditor found in conformity
with his declaration in form ‘I’/‘K’.
(*Strike off, which ever in not applicable)
(Name designation and signature of the Nominated authority)
27. Form ‘I’ in the First Schedule of the Principal Rules is substituted namely:
FORM ‘I’: DECLARATION BY FIRE SAFETY AUDITOR
[See rule 35]
PART-I
(To be filled, for the building issued with Fire Safety Directives U/R 34)
UID No…………………………. Dated: …………….
To
The Director
Delhi Fire Service
Delhi Fire Service Headquarters
Connaught Place
New Delhi-110 001.
Sir,
This is submitted that all the fire prevention and fire safety measures as
recommended by you vide letter No. ………………………………………………………..
dated………………….
have been installed/provided in the building/premise
…………………………………………………………………………………………………………
…… (address of building/premise).The para wise compliance report is enclosed
and it is certified that the performance of all the fire prevention and fire safety
measures are tested in conformity with the provisions of relevant Standards by
undersigned on………………….……., and found in good working condition. I,
…………………………………………..(Name in full) under took that this declaration of
mine, if contravenes with the statuary provisions of the Act and Rules, shall be
liable for penal actions under Rule 35 of Delhi Fire Service Rules -2010.
Enclosed: As Above
Dated:
(Signature of the Fire Safety Auditor) ……………….
Contact details:
Email ID ………………………………………………….
Tel. No. …………………………………………………….
Mobile No. ……………………………….……………….
Fire Safety Auditor Level……Registration No………
Stamp………………………………………………………..
Counter signed by the Owner/occupier
I, …………………………………………..(Name in full) under took that this declaration
of mine, if contravenes with the statuary provisions of the Act and Rules, shall be
liable for penal actions under section 37 of the Delhi Fire Service Act -2007.
Signature………………………………………….
Contact details:
Email ID ………………………………………………….
Tel. No. …………………………………………………….
Mobile No. ……………………………….……………….
PART-II
(To be filled only, if Fire Safety Directives U/R 34
are not issued to the building)
UID No…………………………. Dated: …………….
To
The Director
Delhi Fire Service
Delhi Fire Service Headquarters
Connaught Place
New Delhi-110 001
Sir,
This is to inform you that the building/premise
……………………………………………(name of the building/premise) located
at………………………………………………………………………
(address of the building) comprised of……………….
basement(s)and…………………………………… (upper floors) owned/occupied by
……………………………………………. (name of the company/ name of the
owner/occupier). The details occupancies at each level of building are as under:
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
…………………………………………………………………………………………………………
………………………………………………………………In this connection it is
submitted that all the fire prevention and fire safety measures as applicable
under Rule 33 of DFS Rules have been provided in the building/premises and
para wise compliance report is enclosed. It is certified that the performance of all
the fire prevention and fire safety measures is tested in conformity with the
provisions of relevant Standards by undersigned on………………….……., and
found in good working condition.
Enclosed: As Above
I am also enclosing the following information and documents on which the
applicability of the prevailing building-bye laws on this building/premise is
adjudged by undersigned:
(1) The site plan in accordance with clause 2.0.4 (f) (ii) of UBBL-2016 (as
amended from time to time)
(2) The Certificate by a registered Architect for the height of the building in
accordance with clause 1.4.16 of UBBL-2016.
(3) As built Plans, duly signed by the owner or occupier and by a registered
architect in conformity with clause 2.0.4 (h) of UBBL-2016.
(4) Date of initial operation of occupancies is duly marked on the plans in
conformity with clause 2.0.4 (h) (i) & 1.4.75 of UBBL-2016.
I, …………………………………………..(Name in full) under took that this declaration
of mine, if contravenes with the statuary provisions of the Act and Rules, shall be
liable for penal actions under Rule 35 of Delhi Fire Service Rules -2010.
Enclosed: As Above
Dated:
(Signature of the Fire Safety Auditor) ……………….
Contact details:
Email ID ………………………………………………….
Tel. No. …………………………………………………….
Mobile No. ……………………………….……………….
Fire Safety Auditor Level……Registration No………
Stamp………………………………………………………..
Counter signed by the Owner/occupier
I, …………………………………………..(Name in full) under took that this declaration
of mine, if contravenes with the statuary provisions of the Act and Rules, shall be
liable for penal actions under section 37 of the Delhi Fire Service Act -2007.
Signature………………………………………….
Contact details:
Email ID ………………………………………………….
Tel. No. …………………………………………………….
Mobile No. ……………………………….……………….
28. Form ‘J’ of the First Schedule is substituted namely:
*MR/NMR: Meeting the requirement/Not Meeting the requirement
Notes (if any):
Signature……………….…………….….…….…………
Name of the Fire Safety Auditor….…….…………….
Email ID………………………………………………………
Telephone No……………………………….. …………….
Mobile No…………………………………………………….
Fire Safety Auditor Level……Registration No………
Stamp………………………………………………………..
29. Form ‘K’ of the First Schedule is substituted namely:
FORM ‘K’: YEARLY DECLARATION
[See sub-rule (2) of rule 38]
DECLARATION
UID No.……………………… Date ………………….
It is hereby declared that the …………………………………… (name of the building
or premises) located at…………………………………..
……………………………………………….…….……………………….(address)
Comprised of ………………. basement(s) and …………………… (upper floors) have
complied with the fire prevention and fire safety requirements in accordance with
rule 33 of the Delhi Fire Service Rules, 2010 and issued Fire Safety Certificate
Under Rule 35 vide UIDNO. ………………….…… is valid in accordance with rule
36. The fire prevention and fire safety measures provided in the
building/premises have been checked and tested in accordance with relevant
standards in the presence by owner/occupier on ……………………. and found
them in place and in good repairs. A record for the same is properly maintained
with me as well as with the owner/occupier.
It is further declared that no additions or alterations have been made in the
building/premises affecting the fire prevention and fire safety measures including
the means of escape and that all exits and passages are free from any
obstruction. This declaration is for the period
from……………….….……to……………..…….……….
Name of the *Fire Safety Officer/*Fire Safety Auditor..………….…
Email ID…………………………………………………………
Telephone No………………………………. …………….….
Mobile No……………………………………………………….
*(In case of Fire Safety Auditor) Level ………and Registration
No…………….……………………………….
Stamp………………………………………..
Counter signed(By the owner /occupier)
Signature………………….……………………………
Name in Block Capitals……………………………..
Email ID…………………………………………………..
Telephone No……………………………. …………….
Mobile No…………………………………………………
* Strike out whichever is not applicable.
30. Form ‘L’ of the First Schedule is substituted namely:
FORM ‘L’: FORM OF NOTICE
[See under sub-rule (1) of rule 41]
GOVERNMENT OF NATIONAL CAPITAL TERRITORY OF DELHI
HEADQUARTERS: DELHI FIRE SERVICE, CONNAUGHT PLACE,
NEW DELHI-1100 01
No. Dated:
NOTICE FOR DEMAND OF FEE UNDER SUB-SECTION (2) OF SECTION 22 OF
THE ACT
WHEREAS the services of the Delhi Fire Service were requisitioned
on………………………….……at …………. Hours to assist in the fire fighting and/or
rescue operation during the outbreak of fire……………………………. (address of
the premises).
WHEREAS ………………………………… (no of appliances) along with members of
fire service responded from ……………………………………………… (name of fire
stations) on …………. at ……………………. hours and returned back to their
respective fire stations on……………….. at……………………. Hours.
WHEREAS a sum of ₹……………………………………towards the deployment of the
Fire Service is due to be paid by you.
NOW THEREFORE, I ………………………………………. (name)
………………………………. (Designation) call upon you to pay the said amount
within ………………. days through bank draft payable to DDO (Headquarters),
Delhi Fire Service payable at Delhi or through online payment gateway.
Signature
Director
To
_____________________
_____________________
31. In the First Schedule, Form ‘U’ to be inserted after Form ‘T’
FORM ‘U’
[See rule 35(2)]
APPLICATION FOR REGISTRATION/EMPENELLMENT TO ACT AS FIRE SAFETY
AUDITOR
To
……………………………
……………………………
……………………………
……………………………
Photograph of
the Applicant
Sub: Application for registration as well as empanelment to act as Fire Safety
Auditor.
The undersigned hereby applies for grant of or renewal of registration as well as
empanelment to fulfill the requirement of DFS Rules (Amendment)-2025to act as a
Fire Safety Auditor in any building or part thereof. The particulars regarding the
Agency are given below:
Personal Attributes
Table-1
1. Full Name of the Applicant (In capital letters)
2. Whether Fire Safety Auditor will be a Proprietary
Concern or an Association of persons such as a Firm or
Company, etc.
3. Registration No. of Firm or Company (Copies of
Registration Certificate, article of Association or
another relevant document appended.
4. Address
5. If the Fire Safety Auditor will be:
a) Proprietary concern, the name, qualifications and
address of the person operating the same.
b) A firm or company, names, qualifications and
addresses of each of the partners, or as the case may
be, Directors.
6. Office address from where the Agency will act as a Fire
Safety Auditor
7. Bank Account Details to receive the remuneration
Technical Qualification and Experience
Table-2
1. Level for which registration is applied for
2. Personnel with the Agencya. Supervisory staff, name, qualifications and
addresses of each.
b. Other employees-names, qualifications and
addresses of each.
3. Details of work with regard to fire Prevention and life
safety measures, if any, undertaken and executed
previously.
a. Name or nature of work.
b. Whether the work executed or still in progress and
remains to be executed.
(Note -Original or attested copies of Certificate of
verification of above details)
4. Technical qualifications and experience of the
promoter or partners of directors and dealing
technical officers or employees of or with the
applicant.
Professional Attributes
Table-3
1. Whether enlisted with any other department or
Organization in any other State. If so, in which
category.
a. Has the applicant or his partners or Directors been
blacklisted in the past by any Government
Department/ organization/other State?
b. Has the applicant applied for registration elsewhere
in his name or in the name of partner, Director or
firm or company? If so, whether the application is
rejected? Give particulars.
2. Whether the applicant has produced up to date
Income tax certificate.
3. Amount of indemnity for professional work as Fire
Safety Auditor and date of its validity
4. Transaction ID/details for the fee remitted to act as
Fire Safety Auditor with Authority
5. If the application is for renewal of the existing
registration, the details old registration number and
the period of its validity.
6. Whether, the registration to act as Fire Safety Auditor
granted anytime previously has been
cancelled/blacklisted; and if so, reasons therefor:
Check List and Undertaking
Table-4
1. Attested copy of partnership deed and power of attorney
or articles of association and memorandum of association
or undertaking in case the individual is the sole
proprietor of the firm.
YES/NO
2. Attested copies of education qualifications to act a Fire
Safety Auditor.
YES/NO
3. Certificate regarding experience to act a Fire Safety Auditor. YES/NO
4. Certificates regarding satisfactory completion of works
carried out for the required experience period.
YES/NO
5. Attested passport size photographs of partners or directors
or individual proprietor and also of the professionals.
YES/NO
6. Undertaking, stating that his/her firm is not blacklisted by
any of the departments of the State Government, local
authority or any board or corporation or organization
owned or controlled by the State Government or any other
State Government.
YES/NO
7. Address proof of office/branch in NCT of Delhi. YES/NO
8. List of technical staff with their qualifications YES/NO
9. Copy of indemnity for professional work as Fire Safety
Auditor
YES/NO
10. Any other information and/or documents as may be
required in the form ‘U’.
YES/NO
I/We hereby solemnly declare that all the information and record provided in
form ‘U’ is true to the best of my/our knowledge.
I/We hereby certify that I/We have not been and will not get myself or ourselves
registered as Fire Safety Auditor in the department under more than one name.
*[My previous registration number in Delhi Fire Services …………………for
level…………]
*Strike-off, if not applicable
Thanking you,
Yours faithfully
[Signature, Name and Address of the Applicant(s)]
32.The Second Schedule of the Principal Rules is substituted namely:
SECOND SCHEDULE
Limits and Extent of Fire Zones, Fire Divisions, and Fire Sub-Divisions
[See rule 6]
1. Limits and Extent of Fire Zones:
1) The limit and extent of East Zone shall be the area bound by:
Entire Area of North-East and East Divisions.
2) The limit and extent of West Zone shall be the area bound by:
Entire Area of West, South-West and North West Divisions.
3) The limit and extent of North Zone shall be the area bound by:
Entire Area of North, Outer North and Central North Divisions.
4) The limit and extent of South Zone shall be the area bound by:
Entire Area of South and South East Divisions.
5) The limit and extent of Central Zone shall be the area bound by:
Entire Area of New Delhi, Central and Old Delhi Divisions.
2. Limits and Extent of Fire Divisions:
1) The limit and extent of New Delhi Division shall be the area bound by:
Entire area of New Delhi and Delhi Cantonment Sub- Divisions.
2) The limit and extent of Central Division shall be the area bound by: Entire
area of Patel Nagar and Karol Bagh Sub- Divisions.
3) The limit and extent of Old Delhi Division shall be the area bound by:
Entire area of Sadar Bazaar and Chandani Chowk Sub-Divisions.
4) The limit and extent of North-East Division shall be the area bound by:
Entire area of Karawal Nagar, Gokulpur, Yamuna Vihar and Shahdara
Nagar Sub-Divisions.
5) The limit and extent of East Division shall be the area bound by: Entire
area of Gandhi Nagar, Vishwas Nagar and Patparganj Sub-Divisions.
6) The limit and extent of North Division shall be the area bound by: Entire
area of Burari, Adarsh Nagar and Badli Sub-Divisions.
7) The limit and extent of Outer North Division shall be the area bound by:
Entire area of Mundka, Narela and Bawana Sub-Divisions.
8) The limit and extent of Central North Division shall be the area bound by:
Entire area of Shakur Basti, Shalimar Bagh and Model Town SubDivisions.
9) The limit and extent of South Division shall be the area bound by: Entire
area of Chhatarpur, Malviya Nagar, Deoli and Mehrauli Sub-Divisions.
10) The limit and extent of South East Division shall be the area bound by:
Entire area of Jangpura, Kalkaji and Badarpur Sub-Divisions.
11) The limit and extent of West Division shall be the areaboundby: Entire
area of Vikaspuri, Janakpuri and Rajouri Garden Sub-Divisions.
12) The limit and extent of South-West Division shall be the area bound by:
Entire area of Najafgarh, Matiala, Dwarka and Bijwasan Sub-Divisions.
13) The limit and extent of North-West Division shall be the area bound by:
Entire area of Kirari, Nangloi Jat and Rohini Sub-Divisions.
3. Fire Sub-Divisions: The Fire Sub-Divisions shall have fire stations as
mentioned against in the table below:
S. No. Sub Division Fire Stations Name
1
New Delhi
Rakab Ganj
Chanakyapuri
Connaught Circus
Headquarter
Supreme Court
Rashtrapati Bhawan
Delhi Secretariat
Civic Centre
Delhi High Court
2 Delhi Cantonment *
3
Patel Nagar
Moti Nagar
Moti Nagar-TC/WS
Prasad Nagar
Shankar Road
4
Karol Bagh
J. R. Road
Naraina
5
Sadar Bazaar
Teliwara
SPM
6 Chandni Chowk
Town Hall
Paiwalan
Daryaganj
7 Karawal Nagar *
8
Gokulpur
Gokul Pur
Tahir Pur
9 Yamuna Vihar Yamuna Vihar
10 Shahdara Shahdara
11 Gandhi Nagar
Shastri Park
Laxmi Nagar
Geeta Colony
12 Vishwas Nagar CBD Shahdara
13 Patparganj
Kalyan Vas
Dallupura
Mandawli
Mayur Palace
14 Burari *
15 Adarsh Nagar *
16 Badli
Jahangirpuri
Sanjay Gandhi Transport Nagar
17 Mundka *
18 Narela
Narela
Bhorgarh
19 Bawana
Bawana
DSIIDC Bawana
20 Shakur Basti Paschim Vihar
21 Shalimar Bagh Keshavpuram
Netaji Subhash Palace
22 Model Town
Roop Nagar
Wazirpur
23 Chhatarpur *
24 Malviya Nagar
Malviya Nagar/ Geetanjali
Nehru Place
Bhikaji Cama Palace
25 Deoli *
26 Mehrauli Vasant Kunj
27 Jangpura
AIIMS
Safdarjung
Mathura Road
28 Kalkaji
Okhla
Jasola
29 Badarpur
Sarita Vihar
Okhla Ph-I
30 Vikaspuri Tikri
31 Janakpuri Janakpuri
32 Rajouri Garden
Hari Nagar
Kirti Nagar
33 Najafgarh
Najafgarh
Jaffarpur
34 Matiala *
35 Dwarka
Dwarka
Yashobhoomi (DWK-25)
36 Bijwasan *
37 Kirari
Rohini Sec-41
Mangolpuri
38 Nangloi Jat
Jawalapuri
Jawala Heri
Udhyog Nagar
39 Rohini
Rohini Sec-05
Rohini Sec-16
*Fire Station(s) to be constructed
(4) Limits and Extent of Fire Sub-Divisions:
1) The limit and extent of New Delhi Sub-Division shall be the area bound by
Rakab Ganj, Chanakya Puri, Connaught Circus, Headquarter, Supreme Court,
Rashtrapati Bhawan, Delhi Secretariat, Civic Center & Delhi High Court Fire
Stations.
2) The limit and extent of Delhi Cantonment Sub-Division shall be the area bound
by- *Fire Station(s).
3) The limit and extent of Patel Nagar Sub-Division shall be the area bound Moti
Nagar, Moti Nagar- TC/ WS, Prasad Nagar & Shankar Road Fire Stations.
4) The limit and extent of Karol Bagh Sub-Division shall be the area bound by J.
R. Road and Naraina Fire Stations.
5) The limit and extent of Sadar Bazaar Sub-Division shall be the area bound by
SPM Marg and Teliwara Fire Stations.
6) The limit and extent of Chandni Chowk Sub-Division shall be the area bound
by Town Hall, Paiwalan and Daryaganj Fire Stations.
7) The limit and extent of Karawal Nagar Sub-Division shall be the area bound by
– *Fire Station(s).
8) The limit and extent of Gokul Pur Sub-Division shall be the area bound by
GokulPur & Tahirpur Fire Stations.
9) The limit and extent of Yamuna Vihar Sub-Division shall be the area bound by
Yamuna Vihar Fire Stations.
10) The limit and extent of Shahdara Sub-Division shall be the area bound by
Shahdara Fire Station.
11) The limit and extent of Gandhi Nagar Sub-Division shall be the area bound by
Shastri Park, Laxmi Nagar & Geeta Colony Fire Stations.
12) The limit and extent of Vishwas Nagar Sub-Division shall be the area bound
by CBD Shahdara Fire Station.
13) The limit and extent of Patparganj Sub-Division shall be the area bound by
Kalyan Vas, Dallupura, Mandawali & Mayur Palace Fire Stations.
14) The limit and extent of Burari Sub-Division shall be the area bound by – *Fire
Station(s).
15) The limit and extent of Adarsh Nagar Rohini Sub-Division shall be the area
bound by – *Fire Station(s).
16) The limit and extent of Badli Sub-Division shall be the area bound by
Jahangir Puri & Sanjay Gandhi Transport Nagar Fire Stations.
17) The limit and extent of Mundka Sub-Division shall be the area bound by –
*Fire Station(s).
18) The limit and extent of Narela Sub-Division shall be the area bound by Narela
& Bhorgarh Fire Stations.
19) The limit and extent of Bawana Sub-Division shall be the area bound by
Bawana & DSIIDC Bawana Fire Stations.
20) The limit and extent of Shakur Basti Sub-Division shall be the area bound by
Paschim Vihar Fire Station.
21) The limit and extent of Shalimar Bagh Sub-Division shall be the area bound
by Keshav Puram & Netaji Subhash Palace Fire Stations.
22) The limit and extent of Model Town Sub-Division shall be the area bound by
Roop Nagar & Wazirpur Fire Stations.
23) The limit and extent of Chhatarpur Sub-Division shall be the area bound by-
*Fire Station(s).
24) The limit and extent of Malviya Nagar Sub-Division shall be the area bound
by Geetanjali, Nehru Place & Bhikaji Cama Palace Fire Stations.
25) The limit and extent of Deoli Sub-Division shall be the area bound by- *Fire
Station(s).
26) The limit and extent of Mehrauli Sub-Division shall be the area bound by
Vasant Kunj Fire Station.
27) The limit and extent of Jangpura Sub-Division shall be the area bound by
AIIMS, Safdarjung and Mathura Road Fire Stations.
28) The limit and extent of Kalkaji Sub-Division shall be the area bound by Okhla
and Jasola Fire Stations.
29) The limit and extent of Badarpur Sub-Division shall be the area bound by
Sarita Vihar & Okhla Ph-1 Fire Stations.
30) The limit and extent of Vikaspuri Sub-Division shall be the area bound by
Tikri Fire Station.
31) The limit and extent of Janakpuri Sub-Division shall be the area bound by
Janakpuri Fire Station.
32) The limit and extent of Rajouri Garden Sub-Division shall be the area bound
by Hari Nagar & Kirti Nagar Fire Stations.
33) The limit and extent of Najafgarh Sub-Division shall be the area bound by
Najafgarh & Jaffarpur Fire Stations.
34) The limit and extent of Matiala Sub-Division shall be the area bound by –
*Fire Station(s).
35) The limit and extent of Dwarka Sub-Division shall be the area bound by
Dwarka and Yasho Bhoomi Fire Stations.
36) The limit and extent of Bijwasan Sub-Division shall be the area bound by –
*Fire Station(s).
37) The limit and extent of Kirari Sub-Division shall be the area bound by Rohini
Sec-41 & Mangol Puri Fire Stations.
38) The limit and extent of Nangloi Jat Sub-Division shall be the area bound by
Jawala Puri, Jawala Heri and Udhyog Nagar Fire Stations.
39) The limit and extent of Rohini Sub-Division shall be the area bound by Rohini
Sec-05 & Rohini Sec-16 Fire Stations.
5. Limits and Extent of Fire Stations:
(1) Mayur Place Fire Station: The limits and extent of Mayur Place Fire Station
shall be the area bounded by:
(i) From NE3 to Chand Cinema Road via Patparganj Road (to the south of
Sanjay Park Lake).
(ii) From Chand Cinema Road to Vasundhara Road till UP border.
(iii) Along the UP border to Noida Link Road.
(iv) Noida Link Road to NE3 towards Patparganj Road.
(2) Dallupura Fire Station: The limits and extent of Dallupura Fire Station shall
be the area bounded by:
(i) From Gazipur Gol Chakkar till U.P. border.
(ii) Along the boundary of U.P. border via Pragati Marg (both sides) to Saheed
Captain Sameer Bhan Marg.
(iii) From Saheed Captain Sameer Bhan Marg to Gazipur Gol Chakkar via
Gazipur Road (along the drain).
(3) Kalyan Vas Fire Station: The limits and extent of Kalyan Vas Fire Station shall
be the area bounded by:
(i) From Natraj Chowk (on NE3) to Chand Cinema Road via Patparganj Road.
(ii) From Chand Cinema Road to Khichripur Road
(iii) Khichripur Road to Gurjar Samrat Mihir Bhoj Marg towards Sanjay Lake
Park.
(iv) Gurjar Samrat Mihir Bhoj Marg to Chand Cinema Road.
(4) Mandawali (MIP) Fire Station: The limits and extent of Mandawali Fire Station
shall be the area bounded by:
(i) From Yamuna River Bridge on NH24/ Delhi-Meerut Expressway to UP
Border (Noida).
(ii) Along the boundary of UP border to the Railway line of Anand Vihar Railway
station.
(iii) Along the Railway Line of Anand Vihar Railway station up to Yamuna River.
(5) Laxmi Nagar Fire Station: The limits and extent of Laxmi Nagar Fire Station
shall be the area bounded by:
(i) Master Plan Road to New Patparganj Road Crossing to Swami Dayanand
Marg (Karkari Mor Chowk).
(ii) From Swami Dayanand Marg (towards Mandawali) to the Railway line Anand
Vihar.
(iii) Along the boundary of the Railway line up to Yamuna River.
(iv) Vikas Marg Both Side Up to New Patparganj Road Crossing.
(v) From Yamuna River to Master Plan Road.
(6) CBD Shahdara Fire Station: The limits and extent of CBD Shahdara Fire
Station shall be the area bounded by:
(i) From Krishna Nagar Metro Station (on the junction of Swami Dayanand
Marg & Gurudwara Road) to Maharishi Valmiki Marg to Gurudwara Road to
Maharaja Surajmal Marg up to Delhi Shahdara Outer Cabin Railway line.
(ii) Along the Railway line up to Ch. Charan Singh Marg (Crossing Ghazipur
Drain).
(iii) From Ch. Charan Singh Marg to the crossing of Anand Vihar Railway Station
Line.
(iv) Along the boundary of Anand Vihar Railway Station railway line to Swami
Dayanand Marg.
(v) From Swami Dayanand Marg to Gurdwara Road.
(7) Geeta Colony Fire Station: The limits and extent of Geeta Colony Fire Station
shall be the area bounded by:
(i) Railway Line Pusta Road to Kailash Nagar Railway Line Crossing.
(ii) Railway Line Crossing to Swami Dayanand Marg Upto Master Plan Road.
(iii) Master Plan Road to Pusta Road.
(8) Shahdara Fire Station: The limits and extent of Shahdara Fire Station shall be
the area bounded by:
(i) Main Road Jafrabad Up to BabarPur Road.
(ii) GT Road to Swami Dayanand Marg to Gurudwara Road.
(iii) From the junction of Swami Dayanand Marg & Gurudwara Road to
Maharishi Valmiki Marg to Gurudwara Road to Maharaja Surajmal Marg to
Tahirpur Road (Crossing Delhi Shahdara Outer Cabin Railway line).
(iv) From Tahirpur Road to G T Road Railway Line Crossing.
(v) Along the boundary of the Railway line to Main 100-Feet Road.
(vi) Along the boundary of U.P. Border to Main Mandoli Marg.
(vii) Main 100 Feet Road toNathu Colony Chowk to Durga Puri Chowk.
(viii) Durga Puri Chowk to Babar Pur Road.
(9) Tahirpur Fire Station: The limits and extent of Tahirpur Fire Station shall be
the area bounded by:
(i) GT Road Railway Line Crossing to UP Border to Gagan Vihar Both Side of
Road.
(ii) Border To Mandoli Marg Crossing Wazirabad Road Both Side.
(iii) Along the boundary of UP border to Railway line Crossing Shahdara at
Ghazipur Drain.
(iv) Along the boundary of Railway line Crossing Shahdara to Delhi Shahdara
outer cabin to Tahirpur Road to GT Road Railway Line Crossing.
(10) Gokul Pur Fire Station: The limits and extent of Gokul Pur Fire Station shall
be the area bounded by:
(i) Nathu Colony Chowk to Zafrabad Road Crossing Road No 66.
(ii) Jafrabad Road to Maujpur Main Marg to 5th Pusta Road.
(iii) 5th Pusta Road to Marginal Bandh Road to Karawal Nagar Pusta Road.
(iv) Karawal Nagar Pusta Road to Loni Road Via Jawahar Nagar Upto Border.
(v) Jawahar Nagar Industrial Area to Mandoli Village Via Loni Road.
(11) Yamuna Vihar: The limits and extent of Yamuna Vihar Fire Station shall be
the area bounded by:
(i) Khazoori Khas Metro Station to Wazirabad Road to Gokalpuri Flyover
Shahdra Drain
(ii) Nala Road to Maujpur Babarpur main road junction.
(iii) Maujpur Babarpur main road junction via maujpur/Gamri main road to
5thpushta road junction to khazoorikhas metro station golchakkar.
(12) Shastri Park Fire Station: The limits and extent of Shastri Park Fire Station
shall be the area bounded by:
(i) Old Bridge GT Road Metro Line Crossing to Including Metro Stations to
Jaffarabad
(ii) MCD Colony to Wazirabad Baghpat Marginal Road Crossing.
(iii) Baghpat Road Crossing to Sonia Vihar Pusta Road Up to UP Border (Tronic
City Right Side).
(iv) GT Road to Yamuna Vihar Road.
(13 ) Jasola Fire Station: The limits and extent of Jasola Fire Station shall be the
area bounded by:
(i) From Tughlakabad East Cabin Railway line opposite to Jasola Apollo metro
station road (along the boundary of railway line towards North direction)up
to Mahatma Gandhi Flyover/Mudrika Marg.
(ii) From Mahatma Gandhi Flyover/Mudrika Marg to DND Flyover upto Yamuna
River.
(iii) Along the boundary of Yamuna River to Atlantic World via Kalindi Kunj
Road.
(iv) From Atlantic World via Vishwas Ji Sadak to NH148 towards Apollo
Hospital/Tughlakabad East Cabin Railway line.
(14) Sarita Vihar Fire Station: The limits and extent of Sarita Vihar Fire Station
shall be the area bounded by:
(i) Mathura Road Apollo Hospital Crossing (Sarita Vihar) To Border (Badarpur
Border) Both Sides Along with Railway Track.
(ii) Badarpur Border to Yamuna River
(iii) Along With Yamuna River to Kalindi Kunj Road Crossing to Mathura Road
Apollo Crossing Via Road No 13 A (Sarita Vihar Side).
(15) Okhla Phase –III Fire Station: The limits and extent of Okhla Phase –III Fire
Station shall be the area bounded by:
(i) Outer Ring Road Railway Line to Ma Anandmayee Crossing.
(ii) Ma Anandmayee Marg Upto Okhla Estate Marg Crossing.
(iii) Okhla Estate Marg Crossing to Railway Line (Road No 13 A) Along with
Railway Line Upto Outer Ring Road.
(16) Okhla Phase – I.- The limits and extent of Okhla Phase – I Fire Station shall
be the area bounded by:
(i) Ma Anandmayee Marg and Okhla Estate Marg Crossing to On Ma
Anandmayee Marg Both Sides Upto Border Surrounded by Road No 13
Towards Border and Railway Track (Left-Hand side of Railway track up to
border and Anandmayee Marg)
(ii) Guru Ravi Dass Marg / Okhla Industrial Estate Marg Crossing Towards
Mehrauli Badarpur Road Towards Batra Hospital Up to Deoli Road.
(iii) From Deoli Road to Nai Basti Road to Ch. JuglalBhure Marg to Holi Chowk.
(iv) From Holi Chowk to Shani Bazar Main Road up to Border, Right-hand side
of Deoli-Nai Basti-JuglalBhure-Shani Bazar Road. (Including Asola Wildlife
Sanctuary, Bhatti Mines, Krishna Parvat, Cap Fims Govt. Office, Aravali Hill
View Point Sunrise, Sangam Vihar Church, Sangam Vihar Forest, Neeli
Jheel, Devli)
(v) Along the boundary of Haryana Border up to Railway lines Badarpur.
(17) Nehru Place Fire Station: The limits and extent of Nehru Place Fire Station
shall be the area bounded by:
(i) Modi Flour Mill / Bhaktivedanta Road Crossing to Kalkaji Flyover to Ma
Anandmayee Road to Okhla GolChakkar to Okhla Estate Marg to junction of
Guru Ravi Dass Marg & Okhla Estate Marg.
(ii) From the junction of Guru Ravi Dass Marg & Okhla Estate Marg to
Mehrauli-Badarpur Road.
(iii) From Mehrauli-Badarpur Road to Mandir Marg to Court Chowk Road to DT
Chaurahato Lt. Shaheed Pankaj Juyal Marg to Press Enclave Marg.
(iv) From the Junction of Lt. Shaheed Pankaj Juyal Marg & Press Enclave Marg
to Khirki Main Road to Maharishi Dayanand Marg.
(v) Maharishi Dayanand Marg to Basant Kaur Marg to Shivalik Road to
Inderjeet Verma Marg upto Sri Aurobindo Marg.
(vi) From Sri Aurobindo Marg to Balbir Saxena Marg to August Kranti Marg (Siri
Fort Road) up to BRT Corridor.
(vii) From Joseph Broz Tito Marg to Lala Lajpat Rai Road to Kalka Devi Marg to
Captain Gaur Marg to Modi Flour Mill / Bhaktivedanta Road Crossing.
(18) Malviya Nagar(Geetanjali) Fire Station: The limits and extent of Malviya
Nagar(Geetanjali) Fire Station shall be the area bounded by:
(i) From the junction of Sri Aurobindo & Inderjeet Verma Marg to Geetanjali
Marg (on Shivalik road).
(ii) From Shivalik road to Maharishi Dayanand Marg to Khirki Main Road to
Press Enclave Marg to Late Saheed Pankaj Juyal Marg to Court Chowk
ROAD.
(iii) From Court chowk road to Mandir margto the junction of MB road
(iv) From Deoli Road to Nai Basti Road to Ch. JuglalBhure Marg to Holi Chowk.
(v) From Holi Chowk to Shani Bazar Main Road up to Border, Left-hand side of
Deoli-Nai Basti-JuglalBhure-Shani Bazar Road. (Including Adarsh Enclave,
Radha Swami Satsang, Hanuman Bhakti Mandir, Kholi Dham, Mata Kali
Mandir, Jirkhod Mandir, Dera Village, Sant Hari Das Mandir)
(vi) Along the border of Haryana (Faridabad-Gurgaon Road) to Mehrauli Gurgaon
Rd 148A to Acharya Shri Tulsi Marg to Crescent Road to Sri Aurobindo Marg
up to MMTC/Inderjeet Verma marg.
(19) Vasant Kunj Fire Station: The limits and extent of Vasant Kunj Fire Station
shall be the area bounded by:
(i) From Chattarpur metro station (On Acharya Shri Tulsi Marg) towards Vasant
Kunj Marg to Aruna Asaf Ali Road (enclosing Kishangarh village).
(ii) From Aruna Asaf Ali Marg to Baba Gang Nath Marg to NH 148AE
(iii) From NH 148AE to New Rao Tula Ram Marg Via Palam Fly-over.
(iv) From Rao Tula Ram Marg to NH-48.
(v) From NH-48 to Haryana Border, along the boundary of Haryana
Border to Acharya Shri Tulsi Marg up to Chattarpur Metro Park.
(vi)From Chattarpur Metro Park to Abdul Gaffar Khan Marg/Vasant Kunj Road to
Aruna Asaf Ali Road.
(20) Safdarjung Fire Station: The limits and extent of Safdarjung Fire Station
shall be the area bounded by:
(i) From Race Course Opposite Samrat Hotel at Kemal Ataturk Marg Road
(Upto Drain) To Crossing of Safdarjung Road, Akbar Road, Rajaji Marg,
Teen Murti Marg Via Akbar Road to Crossing of Krishna Menon Marg Via
Tees January Marg Upto Crossing of Janpath and Aurangzeb Road Via
Aurangzeb Road Upto Taj ManSingh Crossing Via Humayun Road Upto
Crossing Subramaniam Bharti Marg Via Subramania Bharti Marg Up to
Crossing of ArchBishop Marg Via Arch Bishop Marg to Lodhi Road
Crossing,
(ii) From Lodhi Road Crossing to the crossing of Lodhi Road and Lala Lajpat
Rai Road.
(iii) Lodhi Road Flyover to Moolchand Crossing Via Lala Lajpat Rai Road (BRT)
And Via Joseph Brij Tito Marg Upto Siri Fort Crossing.
(iv) From Crossing BRT / Siri Fort Road Via Siri Fort Road Up to August Kranti
Marg Crossing.
(v) From Balbir Saxena Marg to Aurobindo Marg up to Green Park Metro
Station.
(vi) From Hukum Chand Marg to Ch. Jhandu Singh Marg/Nauroji Nagar Marg.
(vii) From Crossing of Jhandu Singh Marg and Africa Avenue Road Upto
Crossing of Ring Road and Africa Avenue.
(viii) From Africa Avenue Road Upto Railway Line Both Side Via Hoshiar Singh.
(ix) Area Surrounded Railway Line and Safdarjung Road and Drain Containing
Safdarjung Tomb, Golf Course Etc Excluding Vinay Marg.
(21) Mathura Road Fire Station: The limits and extent of Mathura Road Fire
Station shall be the area bounded by:
(i) Mathura Road Lala Lajpat Rai Road and Dr Zakir Hussain Marg Junction
to Lala Lajpat Rai Road to Moolchand Crossing at Ring Road to Kalka Devi
Marg to Crossing Captain Gaur Marg Upto Modi Flour Mill Crossing to
Railway Line.
(ii) Along the boundary of Railway line up to Mahatma Gandhi
Flyover/Mudrika Marg.
(iii) Mahatma Gandhi Flyover/Mudrika Marg to DND Flyover up to Yamuna
River.
(iv) Along the boundary of Yamuna River to Nizamuddin Bridge
(v) Nizamuddin Bridge to Mahatma Gandhi Road to Bharat Scouts & Guides
Marg (Crossing Railway Line).
(vi) Bharat Scouts & Guides Marg to Sabz Burj Circle to Lodhi Road to Lala
Lajpat Rai Road.
(22) Bhikaji Cama Place Fire Station: The limits and extent of Bhikaji Cama Place
Fire Station shall be the area bounded by:
(i) From the Crossing of Ring Road & Africa Avenue Road to Ch. Chaudhary
Jhandu Singh Road to Green Park Extension Road Towards Mohinder
Hospital Upto Aurobindo Marg Crossing to Adhchini up to Chattarpur
Metro Park.
(ii) From Chattarpur Metro Park to Abdul Gaffar Khan Marg/Vasant Kunj
Road to Aruna Asaf Ali Road.
(iii) Aruna Asaf Ali Road to the crossing of Baba Ganga Nath Marg & Vedant
Desika Mandir Marg.
(iv) Baba Ganga Nath Marg to Nelson Mandela Marg up to Palam Flyover on
New Rao Tula Ram Marg.
(v) From the junction of New Rao Tula Ram and Rao Tula Ram Marg to
Shantipath Crossing on Rao Tula Ram Marg.
(vi) From Shantipath Crossing on Rao Tula Ram Marg to the Crossing of Ring
Road & Africa Avenue Road
(23) Chanakyapuri Fire Station: The limits and extent of Chanakyapuri Fire
Station shall be the area bounded by:
(i) Right Side Samrat Hotel, Ashok Hotel Via Vinay Marg Both Side Upto
Railway Line Yashwant Place Via, Satya Marg to Niti Marg to Crossing at
Shanty Path, Via Shantipath Both Sides Upto Ring Road.
(ii) Crossing Ring Road and Shantipath Via Rao Tula Ram Marg Right Side
Upto Outer Ring Road Crossing (West End Colony) Via Rao Tula Ram Marg
To NH-48 Up to UER-II Including Airport.
(iii) From Area on Left Side Samarat Hotel Via Kautilya Marg Via Teen Murti
Marg Via South Avenue Via DalHousie Road, Via Motilal Nehru Via Krishna
Menon Marg Back Side of Akbar Road (Krishna Menon Lane) Via Rajaji
Marg to Teen Murti Marg Crossing on Teen Murti Lane to Crossing of
Kamal Ataturk Road.
(iv) Junction Of Teen Murti Via Willington Crescent Upto 11 (Eleven) Murti,
From 11 Murti to Mudrika Marg/ Mahatma Gandhi Road to Maude Road
upto the crossing of Thimaya Marg & Cariappa Marg.
(v) From Cariappa Marg Crossing to Shaeed Bhagat Singh Road Up to Railway
line crossing.
(vi) Along the Railway line to UER-II to NH-48.
(24) Narela Fire Station: The limits and extent of Narela Fire Station shall be the
area bounded by:
(i) North East Side of West Yamuna Canal Containing Ghogha, Lampur
Border,Bakner Narela Singhola, Singhu Border, Tajpur Kala, Bakhtawar Pur,
Jhingola to Yamuna River – Ibrahim Pur – Nangli Poona GT Road.
(25) DSIDC Bhorgarh Fire Station: The limits and extent of DSIDC Bhorgarh Fire
Station shall be the area bounded by:
(i) North East Side of West Yamuna Canal Containing Industrial Area Bhorgarh,
Tikri Khurd Shahpur Garhi, Alipur Holambi Kala, Holambi Khurd, and Sanot.
(ii) From Western Yamuna Canal to NH-44 to Bawana-Narela Road to UER-II to
NH-44 (GT Road).
(26) Bawana Fire Station: The limits and extent of Bawana Fire Station shall be
the area bounded by:
(i) Ghevra Railway Crossing (West Side) Containing Rashid Pur, Nizam Pur,
GhariRanhola, TonlyTitesar, Punjab Khor, Qutabgarh, MungeshPur,
AuchandiPur, Harewali, Darya Pur Kalan Bawana – Narela Ghevra Road –
Chandpur – Kanjhawala – Ghevra Crossing.
(27) DSIDC Bawana Fire Station. The limits and extent of DSIDC Bawana Fire
Station shall be the area bounded by:
(i) From Junction Of UER-II and Badli-Bawana Road upto Rohini Heliport to
Narela-Ghevra Road.
(ii) From Narela-Ghevra Road to Western Yamuna Canal including Sultanpur
Dabas, Ishwar Colony.
(iii) Along Western Yamuna Canal to UER-II
(28) Roop Nagar Fire Station: The limits and extent of Roop Nagar Fire Station
shall be the Area Bounded By:
(i) Junction (NH1 and Burari Sant Nagar) – Sant Nagar Burari Road (East Side)
JagatPur, Milan Vihar Upto Yamuna River Including River.
(ii) Baraf Khana – Pul Bangash- Roshanara Road- Area Upto East of Railway
Track –Dilkhush Industrial Area to Junction at NH1 And Burari Transport
AuthorityContaining the entire Delhi University Model Town Shakti Nagar Etc.
(29) Sanjay Gandhi Transport Nagar Fire Station: The limits and extent of Sanjay
Gandhi Transport Nagar Fire Station shall be the area bounded by:
(i) From Shaheed Captain Vikram Batra Chowk (Mukarba Chowk) to Railway
Crossing on Outer Ring Road.
(ii) Along the boundary of Railway line up to Holambi Village Park to Alipur
Chowk via Budhpur-Alipur Road.
(iii) From Alipur Chowk to Budhpur- Narela Road to Nangli Ibrahim Road
towards Nathupura upto Swaroop Nagar Road.
(iv) From Swaroop Nagar Road to Gurudwara Road up to Bhalswa Golf course
on Outer Ring Road including MCD Dump, Bhalswa Dairy & Swaroop
Nagar.
(v) From Outer Ring Road to Shaheed Captain Vikram Batra Chowk (Mukarba
Chowk).
(30) Jahangir Puri Fire Station: The limits and extent of JahangirPuri Fire Station
shall be the area bounded by:
(i) Crossing of Outer Ring Road & Railway Line at Mukarba Chowk to
Gurudwara Road near Bhalswa Lake to crossing of Gurudwara Road &
Swaroop Nagar Road.
(ii) From Swaroop Nagar Road up to the junction of Swaroop Nagar & Dr.
Vinod Kumar Singh Marg to Mangat Ram Marg via Burari Road.
(iii) From Mangat Ram Marg up to Yamuna River including Pardeep Vihar,
Suleman Majra Burari, Badarpur Majra.
(iv) From the other side of Yamuna to Border including Khanpur Tyagi.
(v) Along the boundary of Yamuna River to Sant Nagar Marg to Sant Nagar.
(vi) From Sant Nagar to Outer Ring Road to Mukundpur Flyover to Azadpur
Flyover via Arihant Marg.
(vii) From Railway Line Crossing at Azadpur Flyover to Crossing of Outer Ring
Road Railway line.
(31) Rohini Sector–16 Fire Station. The limits and extent of Rohini Sector – 16
Fire Station shall be the area bounded by:
(i) From Madhuban Chowk to Rohini Heliport.
(ii) From Rohini Heliport to Railway line Crossing via UER-II.
(iii) Along the Railway line to the crossing of Outer Ring Road & Railway Line to
Madhuban Chowk.
(iv) Containing Sector-10,11, 13,14, 15, 16, 17, 18, 27, 28, 29, 30,31, 34, 35,
36, & Badli Industrial Area, DCE Upto The Railway Line (Westside).
(32) Rohini Sector -5 Fire Station: The limits and extent of Rohini Sector -5 Fire
Station shall be the area bounded by:
(i) Junction At Madhuban Chowk to Rohini Heliport via Bhagvan Mahavir
Marg.
(ii) Rohini Heliport to Kanjhawala Industrial Area via Narela Road to Ghevra
Railway Station up to Najafgarh Drain along Railway Line.
(iii) From the crossing of Najafgarh Drain & Kanjhawala Road to Police Line to
Madhuban Chowk.
(33) MangolPuri Fire Station: The limits and extent of MangolPuri Fire Station
shall be the area bounded by:
(i) Junction At Outer Ring Road Near Police Line Bajaj Chowk Via Budh Vihar
Marg
a. Upto Najafgarh Drain (Budh Vihar Nalah) Along with Drain Upto
Railway Line.
(ii) From Railway line to Outer Ring Road Via Mangolpuri Railway Station.
(iii) From Outer Ring Road to Police line junction.
(34) Rohini Sector 41: The limits and extent of Rohini Sec-41 Fire Station shall be
the area bounded by:
(i) Ghevra Railway line towards Bawana via Narela road to Dada Durali Road
(ii) Dada Durali road to UERII to Bhagwan Mahavir Marg Junction to
Kanjhawala UERII Junction.
(iii) Kanjhawala Road Junction to Najafgarh Drain
(iv) Ghevra Railway line to Najafgarh Drain via Railway Line.
(35) Netaji Subash Palace: The limits and extent of Netaji Subash Palace Fire
Station shall be the area bounded by:
(i) MG Marg and Wazirpur flyover junction to Road No.44 and Lala Jagatram
Road junction to Road No.44 and Kabirdas Marg Junction via Road No.44.
(ii) Via Kabirdas Marg to Abdul Hamid Marg and Kabirdas Marg Junction to
Asia Rajmarg via Abdul Hamid Marg.
(iii) Asiaraj Marg to MG Marg and Wazirpur flyover junction.
(36) Udyog Nagar Fire Station: The limits and extent of Udyog Nagar Fire Station
shall be the area bounded by:
(i) From Nangloi Chowk market (on Rohtak road) to Nangloi underpass.
(ii) From Nangloi underpass to Rohtak railway lines (towards Peeragarhi
Chowk fly over)
(iii) From Peeragarhi flyover to Peeragarhi Chowk
(iv) From Peeragarhi Chowk to Nangloi Chowk market.
(37) Keshav Puram Fire Station:The limits and extent of Keshav Puram Fire
Station shall be the area bounded by:
(i) Junction At (Police Line Pitampura and Outer Ring Road) Upto HaiderPur
Nahar (Western Yamuna Canal) Via Outer Ring Road.
(ii) Along With Western Yamuna Canal Via Prembadi Upto Interlock Metro
Station to Swami Narayan Marg to Shastri Nagar Vaishno Temple to
Crossing Of (Kali Dass Marg and Swami Narain Marg) to Old Rohtak Road
from Sarai Rohilla Put to Zakhira Railway Crossing Then Along with
Railway Line (NorthSide Up to Shakur Basti.
(iii) ShakurBasti to Outer Ring Road Police Line Pitam Pura Chowk Via Guru
Harikishan.
(38) Wazirpur Fire Station: The limits and extent of Wazirpur Fire Station shall be
the area bounded by:
(i) West of the Railway Track – North of Najafgarh Drain – South of Ring Road
–Weston Yamuna Canal (East Side) Having Locality Haiderpur Shalimar
Village
(ii) Kela Godown Ring Road, Wazirpur Industrial Area – Ashok Vihar –
Satyawati
(iii) College – Swarm Park – Laxmi Bai College – Shakti Nagar Extension.
(39) PVC Market Tikri Kalan Fire Station: The limits and extent of PVC Market
Tikri Kalan Fire Station shall be the area bounded by:
(i) Ghevra Railway Station to Mundka Village,
(ii) Phirni Road to NilwalPhirni Road to Bahadurgarh Border.
(40) Jawalapuri Fire Station: The limits and extent of Jawalapuri Fire Station
shall be the area bounded by:
(i) Ranhola Village Road Towards Phirni Road,
(ii) Nilothi Village to Phirni Road,
(iii) Saiyyad Nangloi To KeshoPur Nalah Drain (Outer Ring Road)
(iv) Outer Ring Road to Peeragarhi Rohtak Railway Line Upto Ghevra Railway
Station
(v) Ghevra Railway Station to Neelwal Village along the Madanpur Drain.
(41) Paschim Vihar Fire Station: The limits and extent of Paschim Vihar Fire
Station shall be the area bounded by:
(i) Junction At Ordnance Depot and Bharti Vidyapeeth Via Baba Ram Dev Marg
(Raghubir Nagar Marg) Up to Raghubir Nagar Drain Bridge Then Along with
Drain
a. Up to Punjabi Bagh Ring Road
(ii) Punjabi Bagh Ring Road to Railway Line Sakur Basti Via Rohtak Road to
Ordnance Depot and Bhartiya Vidya Peeth Junction.
(42) Jwala Heri Fire Station: The limits and extent of Jwala Heri Fire Station shall
be the area bounded by:
(i) Junction At Ordnance Depot and Bharti Vidyapeeth to junction of
Railway line & Outer Ring Road near Peeragarhi Flyover via Rohtak Road
including New Multa Nagar.
(ii) From Rohtak Road to Najafgarh Drain.
(iii) Along the Najafgarh drain including Sayed Gaon, Bhera Enclave up to
Vikaspuri Flyover.
(iv) From Vikaspuri Flyover to Baba Ramdev Marg to Bharti Vidyapeeth.
(43) Moti Nagar Fire Station: The limits and extent of Moti Nagar Fire Station
shall be the area bounded by:
(i) Junction Of (Railway Line at Transport Centre Punjabi Bagh and Ring Road)
Via Ring Road Upto Drain Behind ESI Hospital Along with Drain Through
Raghubir Nagar To Chaukhandi, Khyala Via Najafgarh Road Upto Moti Nagar
Junction (Moti Nagar Fire Station).
(ii) Moti Nagar Junction to Patel Road to Railway Line ShadiPur Depot to Junction
at Transport Centre Rohtak Road. Punjabi Bagh Including DLF Industrial
Area.
(44) Kirti Nagar Fire Station: The limits and extent of Kirti Nagar Fire Station
shall be the area bounded by:
(i) Junction Fun Cinema Via Natraj Road to Junction at Rama Road to Kirti
Nagar Metro Station to Railway Line and Along with Railway Line Upto Ring
Road Mayapuri Flyover to Ring Road Upto Raja Garden and Shivaji Marg
Crossing.
(ii) Junction At Shivaji Marg to Natraj Crossing.
(45) Training Centre/Workshop Fire Station. The Training Centre/Workshop Fire
Station shall have no operational jurisdiction/ boundary and specialized
firefighting equipment and appliances deployed shall be available for use in any
area on demand
(46) Najafgarh Fire Station: The limits and extent of Najafgarh Fire Station shall
be the area bounded by:
(i) Kakrola Drain (Nalah) Up to Dhansa Badli (Haryana Border) Road, Right
side of Najafgarh Dhansa Road containing Issapur Village, Bakkargarh
Village, Mundhela Kalan Village, Mundhela Khurd, Mitraon, Mitraon
Forest, Surakhpur, Naveen Palace, Jharoda Kalan, Dichaon Kalan.
(ii) Along the border of Haryana towards Bahadurgarh up to Mungeshpur
Drain to BL Bhardwaj Charitable Hospital Road to Bairagi Road to
Najafgarh Road (Kakrola Drain).
(iii) Along the West Bank of Kakrola Drain upto Haryana Border-Along the
boundary of Haryana Border to Ghumanhera Bridge.
(iv) From Ghumanhera Bridge to Saheed Rao Laxmi Chand Marg up to Mitraon
School via Mitra on Phirni Road containing Qutub Vihar, Chhawla,
Kanganheri, Nanakheri, Jhatikra, Shikarpur, Ghumanhera, Asalatpur,
Pandwala Kalan, Kharkhari Nahar, Deenpur, Goyla More, Goyla Dairy.
(47) Janak Puri Fire Station: The limits and extent of JanakPuri Fire Station shall
be the area bounded by:
(i) Junction At Tilak Nagar Police Station and Shivaji Marg to Chaukhandi Road
to Keshav Pur Depot Then Along with Drain Upto Kakrola More.
(ii) Junction At Kakrola More to Shivaji Marg to Railway Line Via Red No 201 Upto
Sagarpur Palam Road and Then Via Sagarpur Palam Road to Nangal Raya to
Jail Road Upto Tilak Nagar Chowk to P. S. Tilak Nagar Via Shivaji Marg.
(48) Hari Nagar Fire Station: The limits and extent of Hari Nagar Fire Station shall
be the area bounded by:
(i) Crossing at Najafgarh Road and Ring Road – Ring Road (West Side) – Crossing
of Railway Track and Ring Road – Area on North Side of Railway Track to
Crossing of Jail Road – Jail Road – Crossing of Najafgarh Road and Ring Road
Containing Rajouri Garden, Mayapuri Industrial Area Phase – I And Phase –II,
Khajan Basti, DTC Colony, Ashok Nagar, Tihar Village, Ashok Nagar Etc.
(49) Dwaraka Fire Sector-6 Fire Station: The limits and extent of Dwaraka Fire
Sector-6 Fire Station shall be the area bounded by:
(i) From Junction At (Kakrola More and Azad Hind Road and Shivaji Marg) to
Najafgarh Drain Via Shivaji Marg Along with East Bank of Drain Passing
Through Kakrola Village Sector 16B, 16C, 16D, 24, Dhul Siras up to UERII.
(ii) UER-II up to Bhartal Underpass (Junction of Railway line and UER-II)
(iii) Along the boundary of the Railway line towards Palam up to Dwarka Road.
(iv) From Bhartal Underpass (Crossing of Railway line and UER-II) Along with
The Railway Line Passing Through Sector 21, Raj Nagar to Road No
201(Palam Najafgarh) Covering Area on West Side of Railway Track Via
Palam Najafgarh Road Up to Kakrola More Junction (Drain) Nala.
(50) Yashobhoomi Fire Station. The limits and extent of Yashobhoomi Fire Station
shall be the area bounded by:
(i) From UER-II at the East Bank of Drain via Bhartal underpass up to NH-48.
(ii) From NH-48 towards Haryana-Gurgaon Border up to Border.
(iii) Along the boundary of Haryana Border crossing Dwarka Expressway up to
Drain.
(iv) Along the East Bank of Drain crossing Najafgarh-Kapashera Road up to
UER-II Containing Bhartal, Dwarka Sec-29,28,25, Yashobhoomi, Bijwasan,
Palam Farms, Salapur Khera Village, Samalka, Kapashera Estate.
(51) Shankar Road Fire Station: The limits and extent of Shankar Road Fire
Station shall be the area bounded by:
(i) Crossing Of Naraina Road and Patel Road Via Patel Road Right Side Upto
Siddhartha Hotel Crossing Via Pusa Road Right Side Area Up to Dayal
Chowk.
(ii) From Dayal Chowk Via Ridge Road Up to Vande Matram Chowk Via
Shankar Road Upto Junction of Mandir Marg and Park Street (Talkatora
Stadium) Ridge Road
(iii) From Vande Mataram Chowk to Simon Bolivar Marg Crossing Via Ridge
Road to Ridge Road Area on Both Sides (All Ridge Area) Up to Dashghara
Via Link Road.
(52) Prasad Nagar Fire Station: The limits and extent of Prasad Nagar Fire Station
shall be the area bounded by:
(i) From Shadipur Depot Upto Railway Line Back Side Of DMS, Patel Nagar
Railway Station Via Prem Nagar, Nehru Nagar Upto New Rohtak Road,
Guru Govind Singh Marg, Via Guru Gobind Singh Marg Upto Liberty
Cinema Via Guru Ravi Dass Marg Upto Crossing of D B Gupta Road
(Khalsa College Chowk).
(ii) From Khalsa College Chowk Via D B Gupta Road to PS Karol Bagh
(iii) From P S Karol Bagh Via Ajmal Khan Road Upto Karol Bagh Metro
Station Area on Right Side
(iv) All W.E.A. Area
(v) Karol Bagh Metro Station to Shadipur Depot Via Pusa Road and Patel Road
Area on Right Side
(53) Naraina Fire Station: The limits and extent of Naraina Fire Station shall be
the area bounded by:
(i) From Brar Square Via Ring Road (M G Road) Both Sides Up to Railway line
Flyover
(ii) From T Point of Ring Road and Naraina Road Via Naraina Road Put Patel
Road Crossing Via Patel Road Towards Shadipur Railway Fly Over Upto
Railway Line.
(iii) From T Point of Naraina Road and Dev Prakash Shastri Marg (Todapur
Road) Upto Dash Ghara Area on Right Side.
(54) Khera Dabar/Jaffarpur Fire Station: The limits and extent of Khera
Dabar/Jaffarpur Fire Station shall be the area bounded
(i) From Mitraon School Bus Stand up to Haryana border on Najafgarh
Dhansa road.
(ii) Along the Boundary of Haryana Border to Dhansa Dam Najafgarh upto
West Bank of Sahibi River Containing Raota, Dauralla, Daurala Village,
Galibpur, Jhuljhuli, Sarangpur, Dhansa, Kazipur, Daryapur Khurd Village,
Jaffarpur Kalan, Kheda Dabar, Ujwa.
(iii) From Ghumanhera Bridge to Saheed Rao Laxmi Chand Marg upto Mitraon
School via Mitraon Phirni Road.
(55) Headquarters Fire Station: The Headquarters Fire Station shall have no
operational jurisdiction/boundary and only specialized fire fighting equipment
and appliances deployed shall be available for use in any area on demand.
(56) Civic Centre Fire Station-
(i) Delhi gate metro station to ITO chowk via Pandit Deen Dayal Upadhyay marg
to minto road junction to Asif ali road golchakkar to Delhi gate metro station.
(57) Delhi Secretariat Fire Station- The limits and extent of Delhi Secretariat Fire
Station shall be the area bounded by:
(i) Delhi Gate Metro Station Via Jawahar Lal Nehru Marg to Satyagrah Marg to
Yamuna Vihar Bank.
(ii) Yamuna Bank Via Vikas Marg to ITO Metro Station Via Bahadur Shah Zafar
Marg to Delhi Gate Metro Station.
(58) Connaught Circus Fire Station: The limits and extent of Connaught Circus
Fire Station shall be the area bounded by:
(i) Junction At Gandhi Museum Ring Road –West Side Area-ITO – Crossing at
Nizamuddin Bridge – North of Sarai Kale Khan – Containing IP Park Upto
Railway Track- Bhairon Marg – Crossing at Mathura Road- Mathura Road –
Sunder Nagar – Oberoi Hotel – Delhi Golf Course – Dr Subramania Bharti
Marg – Humayun Road (North Side Area) – Man Singh Road – Maulana Azad
Road –
(ii) Janpath – Windsor Place – Patel Chowk (East Side) Gurudwara Bangla Sahib –
Kali Bari Marg – Mandir Marg – Ridge Road Towards Dayal Chowk –
Panchkuian Road – Chitragupta Road – D B Gupta Road (South Side) – Pahar
Ganj Chowk New Delhi Railway Station Fly Over – Ajmeri gate Road – Asaf Ali
Road – Delhi Gate – Junction at Gandhi Museum Containing all Areas.
(59) Rakab Ganj Fire Station: The limits and extent of Rakab Ganj Fire Station
shall be the area bounded by:
(i) RML Crossing – 11 (Eleven) Murti Via Willing Don Crescent Area on Both Side
Talkatora Stadium – SPM Stadium. – Junction Of (Park Street, Shankar Road,
Mandir Marg) – Kali Bari Crossing – Kali Bari Road – Gol Dakhana – Patel
Chowk – Windsor Place Junction Via Janpath Up Maulana Azad Road
Crossing – Junction Of Akbar Road / Mansingh Road – Via Mansingh Road –
Taj ManSingh Hotel – Motilal Nehru Marg – Junction (Udyog Bhawan / Air
HQ) – Vijay Chowk – Rail Bhawan Junction Via Red Cross Road – Parliament
Street – Air Line – Gurudwara Rakab Ganj – North Block – Junction At Rakab
Ganj – Via Church Road – North Avenue – RML Crossing.
(60) Rani Jhansi Road Fire Station. The limits and extent of Rani Jhansi Road
Fire Station shall be the area bounded by:
(i) Junction Azad Market (West Side Area) – Chowk Nai Basti – Pahari Dhiraj –
Maha Rishi Balmiki Marg (West Area) – Idgah Road (South Side) – Junction At
New Qutab Road (Area South Side)- Junction (ChelmsFord – D B Gupta Road,
Babu Ram Solanki Road) – D B Gupta Road (North Side Area) – Junction MM
Road Via M Road – Dayal Chowk – Karol Bagh Metro Station (Area On North
Side) – Ajmal Khan Road- Arya Samaj Road Ajmal Khan Road Crossing – Arya
Samaj Road – Junction Guru Ravi Dass Marg / Arya Samaj Road Via Guru
Ravi Dass Marg – D B Gupta Road – New Rohtak Road (Area On North Side) –
Ras Bihari Marg (Area On South Side) – Old Rohtak Road – Ram Bagh Road –
Junction At Azad Market.
(61) Shyama Prashad Mukherjee Marg Fire Station: The limits and extent of
Shyama Prasad Mukherjee Marg Fire Station shall be the area bounded by:
(i) Ajmeri Gate – Ajmeri Gate Road – Lal Kuan Bazar Road – Katra Bariyan Road
– Fateh Puri Chowk – Chandni Chowk Road Up toNetaji Subhash Marg
Crossing – Shyama Prasad Mukherjee Crossing – Yamuna Bazaar Crossing
Upto Yamuna.
(ii) Junction At (Majnu Ka Tilla) – Ring Road – Yamuna Bazaar – Upto Railway
Track Including Yamuna River.
(iii) Majnu Ka Tilla – RajPur Road – Tishazari – Baraf Khana – Pul Bun gushAzad Market – Library Road – Pul Mithai – Naya Bazar – Lahori Gate – Ajmeri
Gate (Shradanand Marg).
(62) Teliwara Fire Station: The limits and extent of Teliwara Fire Station shall be
the area bounded by:
(i) Junction at Pul Mithai, Qutab Road/Azad Market Road – New Qutab Road
Area on West Side of Railway Track – Junction of Idgah Road and New
Qutab Road – Via Idgah Road – Junction of Maha Rishi Balmiki Marg
withIdgah Road – Via Maharshi Balmiki Marg – Chowk Nai Basti – Junction
of Azad Market Via Azad Market Road – Pul Mithai Junction.
(63) Paiwalan Fire Station: The limits and extent of Paiwalan Fire Station shall be
the area bounded by:
(i) Delhi Gate (West Side) – Asaf Ali Road (Back Side)
(ii) Ajmeri Gate – Hauz Quazi (Metro Station) Road – Chawri Bazar – Nai Sarak –
Chandni Chowk Up to Netaji Subhash Marg Crossing – Delhi Gate
(64) Darya Ganj Fire Station: The limits and extent of Darya Ganj Fire Station
shall be the area bounded by:
(i) Delhi Gate East Side Are – Ring Road – Up to Yamuna – Containing All
Samadhi Are – Up to Railway Track – Yamuna Bazaar – Crossing at SPM Road
and Netaji Subhash Marg (Monkey Bridge) Via Netaji Subhash Marg Upto
Delhi Gate Containing Red Fort Darya Ganj.
(65) Town Hall Fire Station- The limits and extent of Town Hall Fire Station shall
be the are bounded by:
(i) SPM Marg & More Serai Road Junction to Chandni Chowk Market Via H.C
Sena Marg.
(ii) Chandni Chowk Market to Chandni Chowk Road & Khari baoli Road
Junction to Swami Vivekenand Marg & Khari Baoli Road Junction to
Railway Road.
(iii) Railway Line to Naya Bazer Road to SPM Marg Junction to More Serai Road
Junction Via Spm Marg
(66)Supreme Court Fire Station: The limits and extent of the Supreme Court Fire
Station shall be limited to the Supreme court only.
(67) High Court Fire Station: The limits and extent of High Court Fire Station
shall be limited to High Court only.
(68) Rastrapati Bhawan Fire Station: The limits and extent of Rashtrapati
Bhawan Fire Station shall be limited to Rashtrapati Bhawan only.
(69) AIIMS Fire Station: The limits and extent of AIIMS Fire Station shall be
limited to AIIMS only.
(70) Fire Safety Management Academy Fire Station: The Fire Safety Management
Academy Fire Station shall have no operational jurisdiction/boundary and only
specialized fire fighting equipment and appliances deployed shall be available for
use in any area on demand.
33.In Clause 7 of the Third Schedule of the Principal Rules, the prescribed
drawings of car flags are added namely:
34.Clause 2 of the Fourth Schedule of the Principal Rules is substituted namely:
2.Enhancement of Deployment Fee. -The deployment fee shall stand enhanced at
the rate of 5% of the fee under sub-clause (1) on first April every year with effect
from first April, 2026”.
35. The Fifth Schedule of the Principal Rules is substituted namely:
FIFTH SCHEDULE
STAND-BY CHARGES ON DEPLOYMENT OF FIRE APPLIANCE
[See sub-rule (1) of rule 20]
1. Deployment of Fire Service on Stand-by duty. – The Director or any other
officer authorized by him in this behalf may on receipt of a request and subject to
availability permit in public interest deployment of fire fighting appliances along
with crew during public functions on payment of charges as mentioned in the
table below:
Sr.
No.
Type of Appliance Charges per six
hours or part
thereof
[Rupees]
Pumping
/Operation
per clock
hour
Other
Charges
[Rupees]
1 Water Tender/
Foam Tender/
Water Bowser
10,000 2,000 @ 50 per liter
foam
concentrate
consumed.
2 Aerial Ladder
/Platform
20,000 5,000 —-
2. Stand-by Charges to be paid in advance. – The payment under sub-clause (1)
shall be made in advance through a bank draft/pay order in favour of DDO
Headquarters, Delhi Fire Service payable at Delhi or through an online payment
gateway.
3. Accommodation for the members of Fire Service. – In case deployment of Fire
Service on stand-by duty exceeds 24 hours in continuation the requesting party
shall make necessary arrangements for the accommodation of the members of
Fire Service free of any charge.
4. Stand-by Duty to be under the charge of a Fire Officer. – The Stand-by duty
shall be under the charge of an officer not below the rank of a sub-officer or
leading fireman or leading fireman/operator.
5. Enhancement of Deployment Fee. -The deployment fee shall stand enhanced at
the rate of 5% of the fee under sub-clause (1) on first April every year with effect
from first April, 2026.
36. The Seventh Schedule shall succeed the Sixth Schedule of the “The Principal
Rules” namely:
SEVENTH SCHEDULE
(See Rule 35)
(Qualification and Experience)
(i) For the purpose of the compliance of Rules 35, 36, 37 and 38by Fire Safety
Auditor; the prescribed minimum qualification, experience and Authorization of
Fire Safety Auditor for the buildings identified under Rule 27 shall be as under:
TABLE-1
Level of Fire
Safety Auditor
and
Authorization
Qualification Experience
(a) Level-1 (L1)-Authorized
for Building or
Occupancy or
Premise
identified in
Rule 27 (3) &
(4) and having
height less
then 15m
i) BE or B. Tech (Fire or Fire Safety)
from a recognized University
OR
(ii) Any Graduate from a University
with Sub-Officer Course from National
Fire Service College Nagpur or
Graduateship of fire Engineering (IFEIndia or UK)
01 Years
Experience in the
relevant field of
Fire Prevention
and Fire Safety.
OR
ii) BE or B. Tech or B. Arch. in Civil or
Mechanical or Electronics or
Architecture with PG Diploma in Fire
and Life Safety Audit from any
University
03 Years
Experience in the
relevant field of
Fire Prevention
and Fire Safety.
(b) Level-2 (L2)-Authorized
for all Building
or Occupancy
or Premise
identified in
Rule 27 having
height less
then 15m
i) Fire Safety Auditor of Level-1 having
any qualification as mentioned above
02 Years
Experience as
Fire Safety
Auditor(L-1)
OR
(ii) B.Sc. (Physics, Chemistry,
Mathematics) with Sub-Officer Course
from National Fire Service College
Nagpur or Graduateship of fire
Engineering (IFE-India or UK)
03 Years
Experience in the
relevant field of
Fire Prevention
and Fire Safety.
OR
ii) Any Graduate from a University
with Station Officer Course or
Divisional Officer Course from
National Fire Service College, Nagpur
or Graduateship of fire Engineering
(IFE-India or UK)
04 Years
Experience in the
relevant field of
Fire Prevention
and Fire Safety.
OR
iii) BE or B. Tech or B. Arch. in Civil
or Mechanical or Electronics or
Architecture with PG Diploma in Fire
and Safety Audit from any University
05 Years
Experience in the
relevant field of
Fire Safety
including
Designing or
Planning or
Installation or
Maintenance of
Fire Prevention
and Fire Safety.
(c) Level-3 (L3)-Authorized
i) Fire Safety Auditor of Level-2 having
any qualification as mentioned above
05 Years
ExperienceasFire
for all Building
or Occupancy
or Premise
identified in
Rule 27
Safety Auditor(
L-2)
OR
(ii) BE or B. Tech (Fire or Fire Safety)
OR
(iii) B.Sc. (Physics, Chemistry,
Mathematics) with Divisional Officer
Course (NFSC)
OR
(iv) Any Graduate from a University
with Membership of Fire Engineering
(IFE-UK)
10 Years
Experience in the
relevant field of
Fire Prevention
and Fire Safety.
Registration, empanelment, Indemnity and Penalty
(i) The Fire Safety Auditor for the purpose of these Rules, having requisite
qualification and experience as prescribed in Table-1, shall apply online to get
themselves registered and empanelled on the portal of Delhi Fire Service by
applying on Form ‘U’ of the First Schedule.
(ii) The registration and empanelment of Fire Safety Auditors shall be valid for a
period of three years from the date of their registration with Delhi Fire Service
unless the Fire Safety Auditor is blacklisted and removed and deregistered from
the panel by the Director. The Fire Safety Auditors shall ensure to get their
empanelment renewed prior to expiry of their registration validity.
(iii) The registration or renewal of registration fee for Fire Safety Auditor shall be
as under:
Table 2(a)
Fire Safety Auditor(Level-1) ₹10,000
Fire Safety Auditor(Level-2) ₹20,000
Fire Safety Auditor(Level-3) ₹30,000
(iv)The Fire Safety Auditor, for their professional work, shall also ensure to
maintain an indemnity insurance bond according to their levels with the Director,
Delhi Fire Services, as mentioned here under for the period of their registration
and empanelment with Delhi Fire Service:
Table 2(b)
Fire Safety Auditor(Level-1) ₹10,00,000
Fire Safety Auditor(Level-2) ₹20,00,000
Fire Safety Auditor(Level-3) ₹30,00,000
The indemnity insurance bond shall be submitted by the Fire Safety Auditor to
the Director Fire Services at the time of seeking empanelment as part of Form ‘U’
submission.
(v) If any non-compliance or deviation from the required fire prevention and fire
safety measures by the Fire Safety Auditor in Form ‘H’ or ‘I’ or ‘J’ or ‘K’ is
reported by the Fire Officer(s),or any falsification by Fire Safety Auditor in any of
Forms as mentioned above or in Form ‘U’ is noted, an explanation of Fire Safety
Auditor will be called through a notice by the Director.
(vi) If, the explanation of the Fire Safety Auditor in reply of Notice as mentioned in
(v), is found unsatisfactory, he will be issued with another notice by the Director
for deposition of penalty amount in conformity with Table 2(c) within 15 days
from the date of this notice. If, Fire Safety Auditor fails to deposit the penalty
amount within the specified time, he will be removed and deregistered from the
panel.
Table 2(c)
Level of Fire Safety Auditor Penalty Amount
Fire Safety Auditor (Level-1) ₹ 2,00,000
Fire Safety Auditor (Level-2) ₹ 5,00,000
Fire Safety Auditor (Level-3) ₹10,00,000
(vii) On second default for the reasons mentioned in (v), an explanation of Fire
Safety Auditor will be called through a notice by the Director and if, the reply of
Fire Safety Auditor is found unsatisfactory, the Fire Safety Auditor is liable to be
blacklisted and deregistered from the panel without issuance of any further
notice by the Director.
Training
(i) The Training of Fire Safety Auditors shall be conducted at Fire Safety
Management Academy, Rohini on the terms and conditions as decided by
Principal of the Academy. The Training charges as stipulated in Sixth Schedule of
DFS Rules shall be borne by the Fire Safety Auditor.
(ii) The Fire Safety Auditor has to successfully complete this training, and the
duration of training for different levels of Fire Safety Auditors is as under:
TABLE-3
Level of Fire Safety Auditor Training Duration
Fire Safety Auditor (Level-1) 03 days
Fire Safety Auditor (Level-2) 05 days
Fire Safety Auditor (Level-3) 07 days
Charges, Remuneration and Ethical Conduct
(i) The Fire Safety Auditor is permitted to charge the owner or occupier of a
premise or building or occupancy for the services provided by it under Rules 35,
36, 37 and 38,as mutually agreed between the Fire Safety Auditor and the owner
or occupier. The charges shall be strictly within the permissible range as
mentioned in Table-4. The agreed charges shall be submitted by the owner or
occupier on the portal of the Delhi Fire Services and the same shall be released
within 24 hours to the engaged Fire Safety Auditor through an automated
process.
TABLE-4
Level of Fire Safety Auditor Range of Charges/Audit
Fire Safety Auditor(Level-1) From ₹10,000 to ₹ 50,000
Fire Safety Auditor(Level-2) From ₹35,000 to ₹90,000
Fire Safety Auditor(Level-3) From ₹63,000 to ₹5,00,000
Note:
1. The above charges shall apply per certification, including issuance of Form ‘H’ or each
annual declaration under Form ‘K’, as applicable.
2. The charges shall be determined by the Fire Safety Auditor based on the height of building,
covered area, occupancy classification, and complexity of fire prevention and fire safety
systems, strictly within the minimum and the maximum limits prescribed herein.
3. The Director may, by order, issue detailed guidelines for objective determination of charges
within the prescribed range.
(ii) On each submission of the documents by the Fire Safety Auditor or the owner
or the occupier as specified under Rule 35(4) or Rule 38(2), the Fire Safety
Auditor shall be remunerated ₹ 500 by the Director, Delhi Fire Service.
(iii) (a) The Fire Safety Auditor are barred from undertaking next two consecutive
certifications (e. g. Form ‘H’ followed by next two Form ‘K’ or Form ‘K’ followed by
next two Form ‘K’) for the same premise or building or occupancy or entity.
(b) The Director may prescribe maximum number of certifications per Fire Safety Auditor per year
to guard against recklessness in issue of certifications.
(iv) The Fire Safety Auditor shall generate a ‘Unique Identification Number’ on all
certification forms bearing his credentials in sequence as mentioned below:
UID No.: Level of the Fire Safety Auditor/Registration number of Fire Safety
Auditor/Calendar Year/Number of renewal by Fire Safety Auditor
e.g., UID No.: L-1or L-2 or L-3/xxxx/20xx/xxxx.
(v) The Fire Safety Auditor has to ensure that for a premise or building or
occupancy or entity on every single occasion of certification, the UID number on
all Forms endorsed by him shall be same.[See rule 35 and 38]
AUTOMATED CONTINUOUS MONITORING SYSTEM
[see rule 37]
1.Automated Continuous Monitoring System (ACMS) based on Internet of Things
(IoT) for the firefighting system in a building or part thereof as specified under
Rule 37 shall be provided for both Active and Passive Measures, ensuring that the
fire prevention and life safety measures are in good repair and efficient working
condition.
2.The provision of the ACMS shall be done in two phases. The installation of
ACMS shall be such that it will give necessary indication to both the owner or
occupier as well as the Fire Safety Auditor, as engaged under Rule 35 in the first
phase. In the second phase, the critical alarms shall also be sent to the Delhi Fire
Service. Details regarding process required in both the phases is given in clause
4. The initiation of the Phase I shall be done with immediate effect of the rules
coming in force whereas phase II shall be done at later stage.
3. The ACMS shall be provided as under:
(a)System Status: The system shall be integrated with requisite mechanism
enabling to know the status of each system which shall be generated and
collected on any suitable IoT Gateway. The data collected shall be uploaded on
any suitable Cloud server which will transmit requisite real time information of
the system health to owner / occupier and the system installer via an email,
short message service (sms) or on mobile through any suitable app service.
Status of following systems shall be notified:
(b)Hydrant:
(i)Main Hydrant Pump run status.
(ii)Standby Diesel/Electrical Pump run status.
(iii)Diesel tank level Monitoring.
(iv)Power to Main Hydrant Pump (On / Off).
(v)Hydrant riser low pressure monitoring.
(vi)Jockey Pump run status.
(vii)Power to Jockey Pump (On/ Off).
(viii)Booster pump Pump run status.
(ix)Power to Main Booster Pump (On/ Off).
(c) Fire Water Tank:
(i)Underground/Above ground Fire Tank Level Monitoring.
(ii)Overhead Tank Low Level Monitoring.
(d) Sprinkler:
(i)Main sprinkler Pump run status.
(ii)Power to main sprinkler pump.
(iii)Sprinkler riser low pressure monitoring.
(e)Detection System:
(i)Detection operation status (On/Off).
(ii)Control Panel/Repeater Panel status (working/nonworking).
(iii)Battery of Control Panel status.
(f) Manual Call Points: Manual Call Points operation Status
(On/Off).
(g) Public Address System: Public Address System status
(working/non-working).
(h)Air Pressurization:
(i)Staircase Pressurization Fan run status for all exits Lift Lobby/
Hoistways.
(ii) Pressurization Fan run status for all Lift Lobby/Hoistway.
(j) Supply and Exhaust Fan: Basement supply and Exhaust Fan Run Status for
Ventilation or Exhaust system.
Note: Following Data parameters will be monitored and sent from local Gateway to
Cloud Portal for Real time monitoring and Report Generation.
I.Mode of Integration:
Sr.
No.
Monitoring of Critical Fire
and Life Safety
Parameters
Mode of Integration
1. Main Hydrant Pump run status Water Differential Pressure Switch
2. Main Sprinkler Pump run
status
Water Differential Pressure Switch
3. Stand by Diesel/Electrical
Pump run status
Water Differential Pressure Switch
4. Jockey Pump run status Water Differential Pressure Switch
5. Booster Pump run status Water Differential Pressure Switch
6. Diesel tank low level Monitoring Level Sensor
7. Power to Main Hydrant Pump Voltage Sensor at Motor Control
Centre (MCC)
8. Hydrant Riser Low Pressure
Monitoring
Pressure Switch/ Transmitter
9. Power to Main Sprinkler Pump Voltage Sensor at MCC
10. Sprinkler Riser Low
Pressure Monitoring less
than 5 Bar
Pressure Switch/ Transmitter
11. UG/AG Fire Tank Low Level
Monitoring System
Ultrasonic water level device
12. Overhead Tank Low Level
Monitoring System
Ultrasonic water level device
13. Detection Operation Status Plain Old telephone Service(POTS)
free contacts from fire panel
14. Control Panel / Repeater Panel
status
Plain Old telephone Service(POTS)
free contacts from fire panel
15. Battery of Control Panel status Plain Old telephone Service(POTS)
free contacts from fire panel
16. Manual Call Points operation
Status
Plain Old telephone Service(POTS)
free contacts from fire panel
17. Public Address(PA) System
status
Fault Status for PA panel
18. Stair case Pressurization
Fan run status for all Exits
Air Differential Pressure Switch
19. Lift Lobby/Hoistway
Pressurization fan run status
Air Differential Pressure Switch
20. Basement Supply and Exhaust
Fan run status for
Ventilation/Exhaust system
Air Differential Pressure Switch
4. Procedural Requirements: The main objective of the IOT base system is to
ensure that fire prevention and life safety systems provided in buildings are
maintained in good repair and efficient working condition for:
(a) Digital Monitoring the Operations of the Fire Fighting Installation and
Equipment;
(b) Digital Maintenance and Record Keeping of Fire Fighting Installation and
Equipment. These can be achieved by adopting following procedure guidelines,
(i) Providing minimum Digital Inputs and Analog Inputs depending upon the
system requirement.
(ii) Machine to Machine communication by following MQTTS Protocol which
will send the Data. MQTTS Protocol to send the Data to cloud portal on real
time basis.
(iii) Connectivity to Cloud Using 4G/5G and above or Ethernet or Wi-Fi or any
other reliable wired or wireless medium which will receive data from IoT
gateway at every 1 min interval.
(iv) Cloud will also send an alarm via SMS if no data is received from the IoT
gateway for more than 15 mins. Cloud portal should generate alarm in case
data is not received for more than specified time so we can ensure
reliability on IoT system.
(v) Gateway should have UPS power and shall have a backup of up to 7 hrs in
case of power failure.
(vi) Gateway shall have an in-built capacity to store a minimum 10000 event
logs.
(vi) It should have real time clock to save data along with time stamp.
(vii) Reports like data report and alarm report should be available from cloud
portal.
(ix) SMS and email alerts option should be available real time basis.
(x) Events should be stored in the Open-Source Database. Uptime should be at
least 99%.
(xi) There should be provision to make API (Application Programming Interface)
in future to send this data to local fire and emergency services. For local
fire and emergency services, alerts should be sent only for critical alarms
e.g. Power Failure to Pumps, Sprinkler and Hydrant Line Pressure Low,
Fault & Fire Conditions of the Fire Alarm System, etc.
By Order and in the Name of the Lt. Governor
of the National Capital Territory of Delhi,
AJAY KUMAR SHARMA, Dy. Secy. (Home)